EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 EVDRIVE03 Electronic expansion valves drivers ENGLISH USER MANUAL ver. 3.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 Important Important Read this document carefully before installing and using the device and follow all the additional information; keep this document close to the device for future consultations. The following symbols support the reading of the document: it indicates a suggestion it indicates an additional information. The device must be disposed according to the local legislation about the collection for electrical and electronic equipment.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 Index 1 INTRODUCTION ................................................................................................................................. 5 1.1 Introduction....................................................................................................................................... 5 1.2 Summarizing table of the main features and available models..................................................................
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 9.7 Algorithm status............................................................................................................................... 53 9.8 Algorithm protection functions ........................................................................................................... 53 9.8.1 LoSH ......................................................................................................................................
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 1 INTRODUCTION 1.1 Introduction The drivers of the EVDRIVE03 series are devices studied for the management of bipolar stepper electronic expansion valves. They are available in built-in and blind version (according to the model). The user interface of the built-in versions consists of a LCD graphic display, of six buttons and guarantees an index of protection IP40. The blind versions must be used with a remote user interface.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 1.2 Summarizing table of the main features and available models The following table shows the main features of the devices and the available models. The character “ / “ means the feature can be set through a configuration parameter. Version (according to the model) built-in LCD • blind • • • • • • User interface 71.0 x 128.0 mm (2.795 x 5.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 2 DESCRIPTION 2.1 Description The following drawing shows the aspect of EVDRIVE03. The following table shows the meaning of the parts of EVDRIVE03.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 3 SIZE AND INSTALLATION 3.1 Size The following drawing shows the size of EVDRIVE03 (4 DIN modules); size in mm (in).
EVCO S.p.A. 3.2 EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 Installation On DIN rail 35.0 x 7.5 mm (1.377 x 0.295 in) or 35.0 x 15.0 mm (1.377 x 0.590 in). To install the device operate as shown in the following drawing. 1 2 To remove the device remove possible extractable screw terminal blocks plugged at the bottom first, then operate on the DIN rail clips with a screwdriver as shown in the following drawing. 3 4 To install the device again press the DIN rail clips to the end first. 3.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 4 ELECTRICAL CONNECTION 4.1 Meaning of the connectors The following drawing shows the connectors of EVDRIVE03. The following tables show the meaning of the connectors; for further information look at chapter 11 “TECHNICAL DATA”. Digital output Electromechanical relay.
EVCO S.p.A. GND AI1 AI2 EVDRIVE03 | User manual ver. 3.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 CAN port line termination (not available in model EPD4BX3) Position microswitch 1 on position on (120 Ω, 0.25 W) to plug in the CAN port line termination (plug in the termination of the first and of the last element of the network). Reserved Reserved.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 Power supply Terminal V≅+ V≅- - Meaning power supply device (not isolated; 24 VAC +10% -15%, 50/60 Hz ±3 Hz, 40 VA max. or 24... 37 VDC, 22 W max.) power supply device (not isolated; 24 VAC +10% -15%, 50/60 Hz ±3 Hz, 40 VA max. or 24... 37 VDC, 22 W max.) protect the power supply with a fuse rated 2 A-T 250 V if the device is powered in direct current, it is necessary to respect the polarity of the power supply voltage.
EVCO S.p.A. 4.2 EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 Example of electrical connection The following drawing shows an example of electrical connection of EVDRIVE03. Please note the power supply of EVDRIVE03 and that of EPS4B are not isolated one another: it is important to wire correctly the devices as indicated in the drawing.
EVCO S.p.A. 4.3 EVDRIVE03 | User manual ver. 3.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 5 USER INTERFACE 5.1 Preliminary information EVDRIVE03 is available in built-in and blind version (according to the model).
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 6 OPERATION 6.1 Switch on and resynchronization At switch-on and after a resynchronization, the fundamental parameters for moving the motor are acquired. The parameters of pressure and temperature units of measure are loaded at switch-on, and, if necessary, is performed the conversion of all the parameters of pressure and temperature.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 The positioning speed depends on the operation mode: - during resynchronization is used the maximum speed, but towards the end of the positioning is made a deceleration ramp - in debug mode is used the speed of the Debug step rate (parameter Prd0) - in manual mode and for all other positioning is used the maximum speed. Using Limit valve opening (parameter Pr30) it is possible to adapt the valve to the application.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 60 reserved 61 SH algorithm 6.3 Stand-by and operation mode selection At the end of the resynchronization operations the machine will enter the stand-by state, during which the installer parameters are loaded and configurations are checked. In this status can be modified the installer parameters, that take effect immediatly, and also the manufacturer parameters, that require a reset.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 6.5 Analog positioner control The analog positioner mode permit to move the valve position linearly respect to the value applied to the active analog input. Pcty = 01 > analog positioner on AI1 (0÷20mA) Pcty = 02 > analog positioner on AI2 (4÷20mA) Pcty = 03 > analog positioner on AI3 (0÷5V) Pcty = 04 > analog positioner on AI4 (0÷10V) Pcty = 05 > analog positioner on AI4 (Pia4).
EVCO S.p.A. 6.7 EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 Manual mode In manual mode (parameter Pr02 = 1), this permits movement of the valve and bringing it to the percentage value stored in Manual set-point position (parameter Pr03) using the maximum step rate. In this mode is active also the control algorithm, but its outputs are unused. 6.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 7 CONFIGURATION 7.1 Preliminary information A complete list of configuration parameters managed by the application is related in the following paragraph, each with a short code, brief description, default values and limits, measurement units (U), the menu in which they are accessed (M) and the notes.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 - if parameters alarm is active, check and correct all the parameters of temperature and pressure, cancel the alarm leading to 1 bit 0 of the variable Command (Cmd), and then reset the EVDRIVE03 - if parameters alarm is cleared check ParS variable and if necessary, reset the board again.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 or and page 8 page 9/11 or page 10/12 The first five pages are dedicated to the end user and permit display of major features of the EVDRIVE03, any alarm messages, or whether it is necessary to resynchronise or reset the machine after changing parameters.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 page 15 page 17 or page 18 or page 19 or page 20 or page 21 These menus permit modification of most driver parameters. In the “Main control parameters” the user can change the control type (analog positioner or SH algorithm), the algorithm sample time, the algorithm parameters set to be used and the parameters for each set, valve start-up position, valve position in case of probe or communication error, valve stand-by position, etc.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 page 23 page 33 or and or page 34 and or page 35 and page 36 ------- page 23 or page 23 page 23 and or to set level 5 password and or to set level 5 password page 37 page 38 The backup and restore functionalities are active only in Stand-by off (10).
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 For further information please consult the hardware manual of the user interface. Operate as follows: 1. Switch off the power supply of the device and of the interface. 2. Connect the device to the interface through the CAN port; look at chapter 4 “ELECTRICAL CONNECTION”. 3. Keep pressed 2 s buttons ESC and RIGHT. 4. Switch on the power supply of the device and of the interface. 5.
EVCO S.p.A. 7.4 EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 Configuring the device through the programming key EVKEY10 The following procedures show how to make the upload and the download of the configuration parameters through the programming key EVKEY10. To copy the parameters from the device to the programming key EVKEY10 operate as follows: 1. Make sure the power supply is switched on. 2. Connect the key to the device; look at paragraph 10.1.4 “Connection to the device”. 3.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 4. Switch on the power supply of the device. 5. Operate as related in the User manual of Parameters Manager. 7.6 Main menu The following procedures show how to gain access to the main menu. The main menu provides information on the project, on the status of the inputs, allows to set the level’s passwords, etc. To gain access to the procedure operate as follows: 1. Make sure the power supply is switched on. 2.
EVCO S.p.A. 7.7 EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 List of configuration parameters The following table shows a full list of configuration parameters. Par. Min. Mas.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 Pp04 -40.0 40.0 °C -40.0 User LOP temperature Pp05 -40.0 40.0 °C 40.0 User MOP temperature Pp13 1.0 100.0 K 40.0 User PID proportional band Pp14 0 999 s 120 User PID integral time Pp15 0 999 s 30 User PID derivative time Pp20 1 255 s 5 Installer start-up delay Pp21 0.00 100.00 % 50.00 Installer start-uo position Par. Min. Mas.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 enable low pressure alarm Pa30 0 1 ---- 0 Installer Pa31 0.00 45.00 barG 0.00 Installer low pressure setpoint alarm Pa32 0.20 1.00 barG 0.30 Installer low pressure alarm hysteresis Pa33 0 250 min 3 Installer low pressure alarm delay Pa40 0 1 ---- 0 Installer Pa41 0.0 10.0 K 1.0 Installer LOP alarm hysteresis Pa42 0 250 min 3 Installer LOP alarm delay Pa50 0 1 ---- 0 Installer Pa51 0.0 10.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 type of refrigerant Pi00 0 19 ---- 0 Manufact. 0 = R-22 1 = R-134A 2 = R-402A 3 = R-404A 4 = R-407A 5 = R-407C 6 = R-410A 7 = R-417A 8 = R-422A 9 = R-422D 10 = R-507A 11 = R-744 12 = R-438A 13 = R-401B 14 = R-290 15 = R-717 16 = R-1270 17 = R-32 18 = R-407F 19 = R-1234ZE driving mode selection Pi01 0 6 ---- 1 Manufact.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 valve selection 0 = generic valve 1 = Sporlan SER AA 2 = Sporlan SER A 3 = Sporlan SER B 4 = Sporlan SER C 5 = Sporlan SER D 6 = Sporlan SERI F 7 = Sporlan SERI G 8 = Sporlan SERI J 9 = Sporlan SERI K 10 = Sporlan SERI L 11 = Sporlan SEHI 175 12 = Sporlan SEHI 400 Pi07 0 28 ---- 1 Costrutt. 13 = Sporlan ESX 14 = Sporlan EDEV B/C (unipolar) 15 = Reserved 16 = Reserved 17 = Sporlan SER 1.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 enabling mode 0 = from free of voltage digital input DI1 or DI2 (stand alone) 1 = from high voltage digital input (stand alone) 2 = from CANBUS 3 = reserved 4 = from RS-485 port with MODBUS 5 = from communication protocol MODBUS protocol via communication external serial interface Pr06 0 9 ---- 0 Manufact.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 Pr51 Pr50 9999 step 1596 Manufact. maximum regulation steps Pr52 Pr51 9999 step 1600 Manufact. overdrive steps Pr53 25 1000 step/s 200 Manufact. stepping rate Pr54 0 1000 mA 120 Manufact. operating phase current Pr55 0 1000 mA 0 Manufact. holding phase current Par. Min. Mas. Unità Default Menu Prd0 25 1000 step/s 25 User debug step rate Prd1 0.00 Prd2 % 0.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 free of voltage digital input DI1 function Ph11 0 4 ---- 1 Manufact. 0 = none 1 = enable/disable valve 2 = change parameters set 3 = resynchronization request 4 = backup battery status free of voltage digital input DI2 logic Ph20 0 1 ---- 0 Manufact. 0 = normally open 1 = normally closed free of voltage digital input DI2 function Ph21 0 4 ---- 2 Manufact.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 analog input AI1 function Piu1 0 4 ---- 1 Manufact. 0 = not used 1 = suction temperature backup probe 2 = suction pressure backup probe analog input AI1 probe type 1 = NTC probe 6 = Pt 1000 probe 10 = 4-20 mA transducer (0.5 - 8 barA) 11 = 4-20 mA transducer (0 - 30 barA) Pia1 1 30 ---- 1 Manufact.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 analog input AI2 function Piu2 0 2 ---- 0 Manufact. 0 = not used 1 = suction temperature backup probe 2 = suction pressure backup probe analog input AI2 probe type 1 = NTC probe 6 = Pt 1000 probe 10 = 4-20 mA transducer (0.5 - 8 barA) 11 = 4-20 mA transducer (0 - 30 barA) Pia2 1 30 ---- 1 Manufact.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 analog input AI3 probe type Pia3 1 6 ---- 1 Manufact. Par. Min. Mas. Unità Default Menu Piu4 4 4 ---- 4 Manufact. 1 = NTC probe 6 = Pt 1000 probe Probe settings: analog input AI4 analog input AI4 function 4 = suction pressure probe analog input AI4 probe type 10 = 4-20 mA transducer (0.5 - 8 barA) 11 = 4-20 mA transducer (0 - 30 barA) 12 = 4-20 mA transducer (-1 - 8 barG) Pia4 10 30 ---- 10 Manufact.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 Par. Min. Mas. Unità Default Menu OfsTs -10.0 10.0 K 0.0 User OfsTe -10.0 10.0 K 0.0 User Par. Min. Mas. Unità Default Menu Mb0a 1 247 ---- 1 Manufact. Probe settings: offset suction temperature offset suction pressure (converted temperature) offset Communication settings MODBUS RS-485 port address MODBUS RS-485 port parity Mb0p 0 2 ---- 2 Manufact.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 CAN baud rate CANb 0 Par. 4 Min. Mas. ---- Unità 1 Manufact. Default Menu 0 = 10K 1 = 20K 2 = 50K 3 = 125K 4 = 500K Command functioning mode Pr02 0 2 ---- 0 User 0 = SH-ALGORITHM 1 = manual mode 2 = debug functionality Pr03 0.00 100.00 % 0.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.
EVCO S.p.A. Psp EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 0.00 100.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 8 SERIAL COMMUNICATION 8.1 Preliminary information It is possible to control the EVDRIVE03 driver by connecting it to a controller. The controller sends information to the driver necessary for its correct functioning, and the driver responds with its internal states, such as (for example) the pressure and temperature measurements, alarms, certain parameters, etc.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 9 ALARMS AND ERRORS 9.1 Alarms and errors The system supports a series of alarms related to both the system (memory, probes, communication, configuration, etc.), and the regulation algorithm (LoSH, HiSH, LOP, MOP, LowPressure). All the alarms, except the parameters alarm (EPar), are automatic, this means that they will be cancelled automatically once the cause of the alarm is removed.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 4 Invalid value for parameter PIA3 5 Invalid value for parameter PIA4 6 PIu1 configured as another Piux Parameters Piu1, Piu2, Piu3 and Piu4 must each 7 PIu2 configured as another PIux have different values, or null. 8 PIu3 configured as another PIux Checked only if Pcty ≥ 6 9 PIu4 configured as another Piux 10 Contradiction between analog input type Check parameters Piax and Piux.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 9.5 Probe error The probe alarm state is monitored every main cycle and is shown in bits 4÷7 of Alarm status (AlSt) and also signalled by the relay, if configured.
EVCO S.p.A. 9.7 EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 Algorithm status Bit 10 of Alarm status (AlSt) is raised for LOP, MOP, LoSH, HiSH, LowPressure or if the measures needed by the algorithm are not valid. This monitoring is in effect only while the system is working in SH-algorithm and in manual mode.
EVCO S.p.A. 9.8.3 EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 LOP When enabled (Pa40), this alarm is triggered when the evaporation temperature (Te) drop below the LOP threshold (Pc04, Pp04, Pd04). The condition is signalled in the Algorithm status (AlgS) and, when the timeout (Pa42) expires, an alarm is set. This protection is most useful during start-up of the machine, when the evaporation temperature is effectively low.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 10 ACCESSORIES 10.1 Programming key EVKEY10 10.1.1 Introduction EVKEY10 is a programming key. Through the key it is possible to make the upload and the download of the application software parameters and / or of the configuration ones. The key can be used on condition that the devices are powered. 10.1.2 Description The following drawing shows the aspect of the programming key EVKEY10.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 10.2 Programming kit EVIF20TUXI 10.2.1 Introduction EVIF20TUXI is a programming kit. Through the kit it is possible to connect the driver to the set-up software system Parameters Manager (using the programming port). The kit is made of: - TTL / USB non optoisolated serial interface - USB cable (to connect the serial interface to the Personal Computer) - TTL cable (to connect the serial interface to the driver). 10.2.
EVCO S.p.A. 10.2.3 EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 Size Size is in mm (in). 10.2.4 Connection to the Personal Computer Operate as follows: 1. Plug in an end of the TTL cable into the TTL port of the serial interface. 2. Plug in the other end of the TTL cable into the programming port of the device. 3. Plug in and end of the USB cable into the USB port of the serial interface. 4. Plug in the other end of the USB cable into an USB port of the Personal Computer.
EVCO S.p.A. 10.3.2 EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 Description The following drawing shows the aspect of the interface EVIF20SUXI. The following table shows the meaning of the parts of the kit. Part Meaning 1 USB cable 2 m (6 ft) long 2 RS-485 cable 2.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 10.3.3 Size Size is in mm (in). 10.3.4 Connection to the Personal Computer Operate as follows: 1.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 10.4 Backup module EPS4B 10.4.1 Introduction EPS4B is a backup module. Through the module it is possible to close the valve in case of lack of power supply of the driver. For further information consult the data sheet of EPS4B. 10.4.2 Description The following drawing shows the aspect of the module EPS4B. The following table shows the meaning of the parts of the module.
EVCO S.p.A. 10.4.3 EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 Size Size is in mm (in). 10.4.4 Connection to the device Look at chapter 4 “ELECTRICAL CONNECTION”Operate as follows: Please note the power supply of EVDRIVE03 and that of EPS4B are not isolated: it is important to wire correctly the devices as indicated in chapter 4.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 11 TECHNICAL DATA 11.1 Technical data Purpose of the device: electronic expansion valves driver. Box: self-extinguishing grey. 71.0 x 128.0 x 60.0 mm (2.795 x 5.039 x 2.362 in; W x H x D); 4 DIN modules. Size: Size refers to the device with the extractable screw terminal blocks properly plugged. Installation: Index of protection: on DIN rail 35.0 x 7.5 mm (1.377 x 0.295 in) or 35.0 x 15.0 mm (1.377 x 0.590 in). IP20; IP40 the front.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 0-5 V ratiometric analog inputs Input resistance: ≥ to 10K Ω. Accuracy: ±1% of the full scale. Resolution: 0.01 V. Conversion time: 100 ms. Protection: against the reversal of polarity. 0-10 V analog inputs Input resistance: ≥ to 10K Ω. Accuracy: ±1% of the full scale. Resolution: 0.01 V. Conversion time: 100 ms. Protection: against the reversal of polarity.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 128 x 64 pixel single colour (black with rearlighting through white signalling LEDs. LEDs) LCD graphic display, signalling LEDs. 1 SPST 5 res. A @ 250 VAC (5 res. A @ 30 VDC) output (electromechanical relay) which can be set via configuration parameter as alarm output/solenoid valve/resynchronization valve. Electromechanical relay Digital outputs: Maximum switching power: 1,250 VA (150 W).
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 2 non optoisolated 1 non optoisolated programming port with MODBUS communication protocol. ports of which 3 1 which 1 CAN port with CANBUS CAN with port CANBUS non optoisolated communication ports protocol, 1 communication RS-485 protocol and 1 communication protocol and 1 programming programming port MODBUS with MODBUS port with port MODBUS with communication protocol. communication protocol.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 EVDRIVE03 Electronic expansion valves drivers User manual ver. 3.4 PT - 30 / 13 Code 144EPDE344 This document is exclusive property of EVCO; reproduction and disclosure are prohibited without express authorisation from EVCO. EVCO is not liable for any features, technical data and possible errors stated in this document or deriving from use of the same.
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344 EVCO S.p.A. Via Feltre 81, 32036 Sedico (BL) ITALY phone +39 0437 8422 | fax +39 0437 83648 email info@evco.it | web www.evco.