7.7 List of configuration parameters
The following table shows a full list of configuration parameters.
Par. Min. Mas. Unità Default Menu Control mode choice
Pcty 0 6 - - - - 6 I
main control type
0 = none
1 = analog positioner on AI1 (0-20 mA)
2 = analog positioner on AI2 (4-20 mA)
3 = analog positioner on AI3 (0-5 V)
4 = analog positioner on AI4 (0-10 V)
5 = analog positioner on AI4
6 = SH control
SetP 1 2 - - - - 1 U
SH parameters set selection
1 = parameters set n. 1
2 = parameters set n. 2
Par. Min. Mas. Unità Default Menu Parameters set n. 1
Pc01 3.0 25.0 K 6.0 User SH setpoint
Pc02 1.0 3.0 K 2.0 User LoSH setpoint
Pc03 10.0 40.0 K 15.0 User HiSH setpoint
Pc04 -40.0 40.0 °C -40.0 User LOP temperature
Pc05 -40.0 40.0 °C 40.0 User MOP temperature
Pc13 1.0 100.0 K 40.0 User PID proportional band
Pc14 0 999 s 120 User PID integral time
Pc15 0 999 s 30 User PID derivative time
Pc20 1 255 s 5 Installer start-up delay
Pc21 0.00 100.00 % 50.00 Installer start-uo position
Par. Min. Mas. Unità Default Menu Parameters set n. 2
Pp01 3.0 25.0 K 6.0 User SH setpoint
Pp02 1.0 3.0 K 2.0 User LoSH setpoint
Pp03 10.0 40.0 K 15.0 User HiSH setpoint