Pa30 0 1 - - - - 0 Installer
enable low pressure alarm
1 = yes
Pa31 0.00 45.00 barG 0.00 Installer low pressure setpoint alarm
Pa32 0.20 1.00 barG 0.30 Installer low pressure alarm hysteresis
Pa33 0 250 min 3 Installer low pressure alarm delay
Pa40 0 1 - - - - 0 Installer
enable LOP alarm
1 = yes
Pa41 0.0 10.0 K 1.0 Installer LOP alarm hysteresis
Pa42 0 250 min 3 Installer LOP alarm delay
Pa50 0 1 - - - - 0 Installer
enable MOP alarm
1 = yes
Pa51 0.0 10.0 K 1.0 Installer MOP alarm hysteresis
Pa52 0 250 min 3 Installer MOP alarm delay
Pa53 0.0 25.0 K 7.0 Installer MOP maximum dSH applicable
Pa54 0.0 25.0 K 8.0 Installer MOP band
Pa55 0 255 10 s 15 Installer MOP filter time constant
Pa56 0 255 min 10 Installer MOP bypass delay
Pa70 0 1 - - - - 0 Installer
enable main power supply alarm
1 = yes
Pa71 0 60 s 1 Installer main power supply alarm delay
Pa75 0 1 - - - - 0 Installer
enable backup battery alarm
1 = yes
Pa76 0 60 s 35 Installer backup battery alarm delay
Par. Min. Mas. Unità Default Menu
Valve and driver: refrigerant
equipment