EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344
page 38 of 70
Pr06 0 9 - - - - 0 Manufact.
enabling mode
0 = from free of voltage digital input
DI1 or DI2 (stand alone)
1 = from high voltage digital input
(stand alone)
2 = from CANBUS
3 = reserved
4 = from RS-485 port with MODBUS
communication protocol
5 = from MODBUS communication
protocol via external serial
interface
6 = from CANBUS + free of voltage
digital input DI1 as consequence of
communication error
7 = reserved
8 = from RS-485 port with MODBUS
communication protocol + free of
voltage digital input DI1 as
consequence of communication
error
9 = from MODBUS communication
protocol via external serial
interface + free of voltage digital
input DI1 as consequence of
communication error
Pr08 0 255 s 1 Installer stabilization delay
Pr09 0.00 100.00 % 50.00 Installer stabilization position
Pr20 0.00 100.00 % 0.00 Installer stand-by position
Pr30 50.00 100.00 % 100.00 Manufact. limit valve opening
Pr40 0 9999 h 0 User working hour (read only parameter)
Pr41 0 365 day 1 Installer
resynchronization interval
0 = disabled
Pr45 30 100 % 100 Manufact. reserved
Pr48 0.00 100.00 % 0.00 Installer communication error position
Par. Min. Mas. Unità Default Menu Valve and driver: generic valve
Pr50 0 Pr51 step 200 Manufact. minimum regulation steps