Installer manual Owner's manual
EVCO S.p.A. EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344
page 51 of 70
4 Invalid value for parameter PIA3
5 Invalid value for parameter PIA4
6 PIu1 configured as another Piux Parameters Piu1, Piu2, Piu3 and Piu4 must
each
7 PIu2 configured as another PIux have different values, or null.
8 PIu3 configured as another PIux Checked only if Pcty ≥ 6
9 PIu4 configured as another Piux
10 Contradiction between analog input type Check parameters Piax and Piux.
(Pia1) and its utilization (Piu1)
11 Contradiction between analog input type Temperature is measured using probes of
(Pia2) and its utilization (Piu2) type NTC, pt1000, or scaling; pressure
12 Contradiction between analog input type is measured using current, tension or scaling
(Pia3) and its utilization (Piu3) probes.
13 Contradiction between analog input type Checked only if Pcty ≥ 6
(Pia4) and its utilization (Piu4)
14 Awaiting AI1 configuration Wait
15 Awaiting AI2 configuration Wait
16 Awaiting AI3 configuration Wait
17 Awaiting AI4 configuration Wait
18 Awaiting analog inputs configurations Wait
19 Limit error Xmax probe scaling
20 Limit error Xmax probe scaling
21 No AI configured for primary temperature Check PIu1, PIu2, PIu3 and PIu4 parameters
or pressure probe input and ensure one is
dedicated to the primary temperature probe,
and another to the primary pressure probe.
Checked only if Pcty ≥ 6
9.4 Communication error
A communication error is signalled only if a suitable communication mode is selected (Pr06 ≥ 2), and the
communication alarm is active (Pa01 = 1). Under these conditions, the driver expects the controller to periodically
refresh the Enable valve command (EnaV).
If the refresh does not happen for more than half the time set in Communication alarm delay (Pa02), a warning is
given. If the refresh does not happen for more than the time set in Communication alarm delay (Pa02), the
communication is considered lost and communication alarm is set.
Management of this alarm depends on the mode selected. If Pr06 = 2÷5, a communication alarm state will cause the
valve to be forced to the position determined by Communication error position (Pr48), and will then enter the
Communication alarm (5) until the positioning process has completed and the communication start again. If Pr06 =
6÷9, a communication alarm status will place the valve into standalone mode, and DI1 enable the valve.
When the communication alarm is cleared, the valve will automatically return to the online mode.
The significance of bit 3 and 2 of Alarm status (AlSt) are shown in the following table:
bit3 bit2 Significance
0 0 No communication alarm
0 1 Warning
1 0 Communication alarm in standalone mode
1 1 Communication alarm