User Manual

9 WORKING SETPOINT AND CONFIGURATION PARAMETERS
9.1 Working Setpoint
MIN. MAX. U.M. DEF. WORKING SETPOINT
r1 r2 °C/°F (1) 0,0 working setpoint; see also r0 and r12
9.2 Parametri di configurazione
PARAM. MIN. MAX. U.M. DEF. WORKING SETPOINT
SP r1 r2 °C/°F (1) 0,0 working setpoint; see also r0 and r12
PARAM. MIN. MAX. U.M. DEF. ANALOG INPUTS
CA1 -25 25,0 °C/°F (1) 0,0 room probe offset
CA2 -25 25,0 °C/°F (1) 0,0 if P4 = 1, evaporator probe offset
if P4 = 2, condenser probe offset
P0 0 1 - - - 1 probe type (0 = PTC; 1 = NTC)
P1 0 1 - - - 1 degree Celsius decimal point (during normal operation)
1 = YES
P2 0 1 - - - 0 unit of measurement for temperature (2)
0 = °C (Celsius degree; resolution depends on P1 parameter)
1 = °F (Fahrenheit degree; resolution is 1 °F)
P4 0 2 - - - 0 second input function
0 = digital input (door switch or multifunction)
1 = analog input (evaporator probe)
2 = analog input (condenser probe)
P5 0 2 - - - 0 magnitude displayed during normal operation
0 = room temperature
1 = working setpoint
2 = if P4 = 0, “- - -
if P4 = 1, evaporator temperature
if P4 = 2, condenser temperature
P8 0 250 0,1 s 5 delayed display of temperature changes as detected by the probes
PARAM. MIN. MAX. U.M. DEF. MAIN REGULATOR
r0 0,1 15,0 °C/°F (1) 2,0 working setpoint differential; see also r12
r1 -99 r2 °C/°F (1) -40 minimum working setpoint
r2 r1 99,0 °C/°F (1) 50,0 maximum working setpoint
r4 0,0 99,0 °C/°F (1) 0,0 working setpoint increase during the “energy saving" function; see also i0, i10
and HE2
r5 0 1 - - - 0 cooling or heating operation (3)
0 = cooling
1 = heating
r12 0 1 - - - 1 working setpoint differential type
0 = asymmetric
1 = symmetric
PARAM. MIN. MAX. U.M. DEF. COMPRESSOR PROTECTION SYSTEM
C0 0 240 min 0 delay in switching on of compressor after the device switches on (4)
C2 0 240 min 3 minimum compressor switch-off duration (5)
C3 0 240 s 0 minimum duration of compressor switch on time
C4 0 240 min 0 duration of compressor switch off time during a room temperature probe error
(code “Pr1”); see also C5
C5 0 240 min 10 duration of compressor switch on time during a room temperature probe error
(code “Pr1”); see also C4
C6 0,0 199 °C/°F (1) 80,0 condenser temperature is higher than that at which the condenser overheat-
ing alarm is activated (code “COH”) (6)
C7 0,0 199 °C/°F (1) 90,0 condenser temperature above which the compressor shut down alarm is
activated (code “CSd”)
C8 0 15 min 1 compressor shut down alarm delay (code “CSd”) (7)
PARAM. MIN. MAX. U.M. DEF. DEFROST
d0 0 99 h 8 if d8 = 0, 1 or 2, defrost interval
0 = interval defrost will never be activated
if d8 = 3, maximum defrost interval
d2 -99 99,0 °C/°F (1) 2,0 evaporator temperature at end of defrost; see also d3
d3 0 99 min 30 if P4 = 0 or 2, defrost duration
if P4 = 1, maximum defrost duration; see also d2
0 = defrost will not be activated
d4 0 1 - - - 0 defrost when device is switched on (4)
1 = YES
d5 0 99 min 0 if d4 = 0, minimum time between switching on of device and activation of
defrost (4)
if d4 = 1, delay in activation of defrost after device is switched on (4)
d6 0 2 - - - 1 temperature displayed during defrost (only if P5 = 0)
0 = room temperature
1 = if on activation of defrost, the room temperature is below the “work
setpoint + + t”, at maximum “ work setpoint + t”; if on activation
of defrost, the room temperature is above “work setpoint + t”, at
maximum the room temperature on activation of defrost (8) (9)
2 = label “dEF
d7 0 15 min 2 dripping duration (during dripping the compressor will remain switched off)
d8 0 3 - - - 0 defrost activation methods
0=AT INTERVALS - FOR TIME - defrost will be activated once the device
has altogether been running for time d0
1=AT INTERVALS - FOR COMPRESSOR SWITCH-ON - defrost will be
activated once the compressor has altogether been switched on for
time d0
2=AT INTERVALS - FOR EVAPORATOR TEMPERATURE - defrost will be
activated when the evaporator temperature has remained below
the temperature d9 for a total time of d0 (10)
3=ADAPTIVE - defrost will be activated at intervals, whose duration will
each time depend on the duration of compressor switch-ons, the evapo-
rator temperature and the door switch input activation; see also d18,
d19, d20, d22, i13 and i14 (10)
d9 -99 99,0 °C/°F (1) 0,0 evaporator temperature is higher than that at which the defrost interval counter
is suspended (only if d8 = 2)
d11 0 1 - - - 0 defrost alarm switches off once maximum time limit has been reached (code
dFd”; only if P4 = 1 and in absence of evaporator probe error (code “Pr2”)
1 = YES
d18 0 999 min 40 defrost interval (defrost will be activated when the compressor has been on
totally, with the evaporator temperature below that of d22, for time d18; only if
d8 = 3)
0 = defrost will never be activated due to the effect of this condition
d19 0,0 40,0 °C/°F (1) 3,0 evaporator temperature below which the defrost is activated (relative to the
evaporator temperatures average, or “evaporator temperatures average - d19”;
only if d8 = 3)
d20 0 999 min 180 minimum consecutive time the compressor must be switched on such as to
provoke the defrost activation
0 = defrost will never be activated due to the effect of this condition
d22 0,0 19,9 °C/°F (1) 2,0 evaporator temperature above which the defrost interval count shall be sus-
pended (relating to the average of evaporator temperatures, that is to say,
"evaporator temperatures average + d22”; only if d8 = 3); see also d18
PARAM. MIN. MAX. U.M. DEF. TEMPERATURE ALARMS (11) (12)
A1 0,0 99,0 °C/°F (1) 10,0 room temperature below which the minimum temperature alarm is triggered
(code "AL"; it concerns the working setpoint, that is to say, "working setpoint -
A1"); see also A11
0 = alarm absent
A4 0,0 99,0 °C/°F (1) 10,0 room temperature above which the maximum temperature alarm is triggered
(code “AH”; it concerns the working setpoint, that is to say, "working setpoint +
A4”); see also A11
0 = alarm absent
A6 0 99 10 min 12 delay in maximum temperature alarm (code “AH”) after the device is switched
on (4)
A7 0 240 min 15 minimum temperature alarm delay (code "AL") and maximum temperature
alarm delay (code "AH")
A11 0,1 15,0 °C/°F (1) 2,0 differential of A1 and A4 parameters
PARAM. MIN. MAX. U.M. DEF. DIGITAL INPUTS
i0 0 4 - - - 1 effect caused by the activation of the digital input
0 = no effect
1=DOOR SWITCH - DOOR SWITCH INPUT ALARM ACTIVATION (code “id”)
- the compressor will be switched off (at maximum for time i3 or until
the input is deactivated); see also i2 (13)
2=MULTIFUNCTION - ACTIVATION OF “ENERGY SAVING” FUNCTION - the
“energy saving” function will be activated (just with effect on the
compressor, until the input is deactivated); see also r4
3=MULTIFUNCTION - ACTIVATION OF MULTIFUNCTION INPUT ALARM (code
iA”) - the device will continue to operate normally; see also i2
4=MULTIFUNCTION - ACTIVATION OF THE MAXIMUM PRESSURE SWITCH
ALARM (code “iA”) - the compressor will be switched off (until the input
is deactivated); see also i2
i1 0 1 - - - 0 type of digital input contact
0 = normally open (active input with closed contact)
1 = normally closed (active input with open contact)
i2 -1 120 min 30 if i0 = 1, delay in signalling of door switch input alarm (code “id”)
-1 = the alarm will not be signalled
if i0 = 3, delay in signalling of multifunction input alarm (code “iA”)
-1 = the alarm will not be signalled
if i0 = 4, delay in switching off of compressor after the activation of the
maximum pressure switch alarm (code “iA”)
-1 = reserved
i3 -1 120 min 15 maximum duration of the effect caused by the activation of the door switch input
alarm (code “id”) on the compressor
-1 = the effect will last until the input is deactivated
i10 0 999 min 0 time that must pass in absence of door switch input activations (after the room
temperature has reached the working setpoint) for the “energy saving” function
to be activated; see also r4 and HE2
0 = the function will never be activated due to the effect of this condition
i13 0 240 - - - 180 number of door switch input activations such as to provoke the defrost activation
0 = defrost will never be activated due to the effect of this condition
i14 0 240 min 32 minimum duration of the door switch input activation such as to provoke the
defrost activation
0 = defrost will never be activated due to the effect of this condition
PARAM. MIN. MAX. U.M. DEF. ENERGY SAVING
HE2 0 999 min 0 maximum duration of the “energy saving” function activated due to the effect of
absence of door switch input activation; see also r4 and i10
0 = the function will last until the input is activated
HE3 0 240 min 2 time interval with no key strokes, after which the "low consumption" function is
activated
0 = the mode shall never be aactivated
PARAM. MIN. MAX. U.M. DEF. VARIOUS
POF 0 1 - - - 1 key activation
1 = YES
PAS -99 999 min -19 access password for the configuration parameters
0 = the password need not be set
EVCO S.p.A. | Code 1043B31E103 | Page 2 of 2 | PT 43/14
This document is exclusive property of EVCO. EVCO does not assume any liability regarding possible errors stated.
The customer (manufacturer, installer or final user) assumes all liability regarding configuration of the device.
EVCO does not take any responsibility for damages coming by the non-observance of additional information.
EVCO reserves the right to make any change without prejudice the basic safety and operating features.
EVCO S.p.A.
Via Feltre 81, 32036 Sedico (BL) ITALY
phone +39 0437 8422 | fax +39 0437 83648
email info@evco.it | web www.evco.it
Notes:
(1) the unit of measurement depends on P2
(2) properly set the parameters corresponding to the regulators after setting P2 parameter
(3) if r5 parameter is set at 1, the “energy saving" function and the defrost management will be switched off
(4) the parameter has effect even after an interruption in the power supply that occurs while the device is switched on
(5) the time set by paramenter C2 is counted also when the device is off
(6) the differential of C8 parameter is 2.0°C/4°F
(7) if when the device is switched on, the condenser temperature is already above that established in C7 parameter,
then C8 parameter will not have effect
(8) the value t depends on r12 parameter (r0 if r12 = 0, r0/2 if r12 = 1)
(9) the display restores normal operation when, at the end of the dripping phase, room temperature falls below the
value that locked the display (or if a temperature alarm is triggered)
(10) if P4 parameter is set at 0 or 2, the device will function as if d8 parameter were set at 0
(11) during defrost and dripping, the maximum temperature alarm is absent, provided that it was triggered after defrost
activation.
(12) during activation of the door switch input, the maximum temperature alarm is absent, provided the alarm was
signaled after the activation of the input
(13) the compressor is switched off 10 s after the activation of the input.