EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 Important Read this document thoroughly before installation and before use of the device and follow all recommendations; keep this document with the device for future consultation. Only use the device in the way described in this document; do not use the same as a safety device. Disposal The device must be disposed of in compliance with local standards regarding the collection of electric and electronic equipment.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 Index 1 INTRODUCTION .............................................. 4 1.1 Introduction ................................................... 4 1.2 Summary table of available models, their main characteristics and purchase codes .................... 5 2 DESCRIPTION ................................................. 8 2.1 Outward appearance description ....................... 8 2.2 Interior description ..............................
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 1 INTRODUCTION 1.1 Introduction EVBOX1 is a line of front mounted electrical boards for the management of cold rooms with single-phase compressor. The user interface comprises a large custom display (with decimal point and function icons), six keys, and has a guaranteed IP65 protection grade front part. The boards are equipped with two 30A res.
EVCO S.p.A. 1.2 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 Summary table of available models, their main characteristics and purchase codes EVB1204N9 EVB1214N9 EVB1206N9 EVB1216N9 EVB1226N9 EVB1236N9 EVB1246N9 EVB1256N9 EVB1204N9 EVB1214N9 EVB1206N9 EVB1216N9 EVB1226N9 EVB1236N9 EVB1246N9 EVB1256N9 The following table contains a description of the available models.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 load 5 (default to condenser fan) (3) 8A 8A 8A 8A 8A 8A load 6 (default to alarm ) (3) 8A 8A 8A 8A 8A 8A • • • • • • Communication ports RS-485 MODBUS for other EVCO products • • Other characteristics clock • alarm buzzer • • • • • three-phase defrost elements management • • • • • integrated driver for unipolar stepper electronic expansion valves.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 Add "M" for the magneto-thermal switch or "D" for the differential magneto-thermal circuit breaker. For additional models, please contact the EVCO distribution network page 7 of 88 EVB1256N9 EVB1246N9 EVB1236N9 EVB1226N9 EVB1216N9 EVB1206N9 Available models EVB1214N9 EVB1204N9 The following table shows the purchase codes.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 2 DESCRIPTION 2.1 Outward appearance description The following drawing shows the outward appearance of the devices.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 12 settings key, hereinafter also "SET" key 13 decrease key, hereinafter also "DOWN" key 14 seal 15 if present, magneto-thermal switch or differential magneto-thermal circuit breaker 16 front shell 17 back shell For additional information, please refer to the following chapters.
EVCO S.p.A. 2.2 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 Interior description To access the interior of the devices, proceed as follows (numbers in parentheses refer to the part number shown in the tables in paragraph 2.1 “Outward appearance description"): 1. Open the access door of the magneto-thermal switch or differential magneto-thermal circuit breaker (1) using the relevant handle (4) and loosen the two screws fastening the front shell to the back shell (2) with a screwdriver. 2.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 if present, K5 digital output (can be set through a configuration parameter to demister heating elements, auxiliary, alarms, 31 door resistors, neutral area operation resistors, condenser fan, compressor 2, defrosting 2, evaporator fan 2, pump down valve, on/stand-by or man in cold room; manufacturer default is condenser fan).
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 3 DIMENSIONS AND INSTALLATION 3.1 Dimensions The following drawing shows the measurements of the devices, in mm (in). 3.2 Installation The unit is designed to be wall mounted, with bolts and fastening screws (not supplied). To install the devices, proceed as follows (numbers in parentheses refer to the part number shown in the tables in chapter 2 "DESCRIPTION"): 1.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 3.3 Installation warnings - make sure that the device work conditions (temperature of use, humidity, etc.) lie within the limits indicated; see chapter “TECHNICAL DATA” - do not install the device near to any heat sources (heating elements, hot air ducts etc.), equipment containing powerful magnets (large diffusers, etc.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 4 ELECTRIC CONNECTION 4.
EVCO S.p.A. 4.2 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 Electric connection for models EVB1204N9 and EVB1214N9 The following drawing shows the electric connections for the EVB1204N9 and EVB1214N9 models.
EVCO S.p.A. 4.3 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 Electric connection for models EVB1206N9 and EVB1216N9 The following drawing shows the electric connections for the EVB1206N9 and EVB1216N9 models.
EVCO S.p.A. 4.4 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 Electric connection for models EVB1226N9 and EVB1236N9 The following drawing shows the electric connections for the EVB1226N9 and EVB1236N9 models.
EVCO S.p.A. 4.5 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 Electric connection for models EVB1246N9 and EVB1256N9 The following drawing shows the electric connections for the EVB1246N9 and EVB1256N9 models.
EVCO S.p.A. 4.6 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 Electric connection for models with magneto-thermal switch or differential magneto-thermal circuit breaker (example for EVB1256N9D) The following drawing shows the electric connections for models with magneto-thermal switch or differential magneto-thermal circuit breaker (example EVB1256N9D).
EVCO S.p.A. 4.7 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 Insertion of the RS-485 MODBUS port termination resistor To reduce reflections on the signal transmitted through the cables connecting the devices to a RS-485 network it is necessary to insert the termination resistor of the first and last elements of the network. To insert the termination resistor place the jumper as shown in the following drawing. 4.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 5 FIRST USE 5.1 First use Operate as follows: Install the device as described in chapter "DIMENSIONS AND INSTALLATION" , following in particular the instructions of 1. paragraph “Installation warnings”. 2.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 6 USER INTERFACE 6.1 Preliminary notes Operating Statuses: - “on” state (the device is powered and is on: the regulators can be switched on) - “stand-by” status (the device is powered but is switched off via software: the regulators are switched off; the possibility to turn the room light or the auxiliary output on/off manually depends on parameter u2) - the “off” status (the device is not powered).
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 The following table shows the correspondence between the labels and the magnitudes displayed. LABEL MAGNITUDE room/inflowing Pb1 air temperature; see also parameter P4 Pb2 evaporator temperature Pb3 auxiliary temperature; see also parameter P4 Pb4 CPT temperature; see also parameter P4 Pb5 if present, vapour pressure Pb6 if present, evaporation temperature Press and release the key “SET”. 4. To exit the procedure: 5.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 During the "rapid cooling" function the work set point is decreased by the temperature set with the r5 parameter; the function runs for the span of time set with the r6 parameter. During the "rapid cooling" function the defrosting function is never activated; if the defrosting interval expires while the rapid cooling function is in progress, the defrosting shall be activated at the end of the cooling. 6.
EVCO S.p.A. 2. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 Keep the "AUXILIARY" key pressed for 2 s: the "AUX1" and/or "AUX2" LEDs shall light up and the heating elements be turned turned on, both for the length of time set with the parameter u6. The demister heating elements cannot be turned off in manual mode (that is to say, before the time set with the parameter u6 has expired). 6.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 - see information regarding the HACCP alarms - cancellation of HACCP alarm list - display of compressor operation hours - cancellation of compressor operation hours - set the working set point (with the procedure described in paragraph “Setting the working set point”). The operations cause the display of the label “Loc” for 1 s. To unlock the keyboard: 3.
EVCO S.p.A. 7 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 OPERATION HIGH WITH LOW RELATIVE OR HUMIDITY PERCENTAGES (ONLY IF THE F0 PARAMETER IS SET TO 5) 7.1 Preliminary notes During operation with a low relative humidity percentage, the evaporator fan shall be turned on if the compressor is on, and shall turn on cyclically if the compressor is off (the F4 parameter determines the duration of the off phase of the fan and the F5 parameter determines the on phase).
EVCO S.p.A. 8 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 “ENERGY SAVING” FUNCTION 8.1 10 Preliminary notes “HACCP” FUNCTION 10.
EVCO S.p.A. 10.2 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 Display of HACCP alarm information To begin the procedure: 1. Make sure that the keyboard is not locked and that no procedure is in progress. Hold the key “DOWN” for 1 s: the display will show 2. the first label available. 3. Press and release the "UP" or "DOWN" key to select “LS”. 4. Press and release the “SET” key: in the models without a clock the 4.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 dur the display is about to show the alarm duration h01 the alarm lasted for 1 hour (continue...) n15 the alarm lasted 1 hour and 15 min code the alarm selected the displays each piece of information for 1 s. To exit the information sequence: 7. Press and release the “ON/STAND-BY”: the display will show the alarm selected. To exit the procedure: 8. Exit the information sequence. 9.
EVCO S.p.A. 11 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 COMPRESSOR OPERATING HOURS COUNT 11.1 Preliminary notes The device can memorise up to 999 comp. operating hours. The parameter C10 establishes the number of operating hours is higher than the limit at which the need for maintenance is signalled. 11.2 Display of Compressor Operation Hours To display the compressor operation hours, proceed as follows: Make sure that the keyboard is not locked and that 1.
EVCO S.p.A. 11.3 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 Cancelling the compressor operation hours To cancel the compressor operation hours, proceed as follows: 1. Make sure that the keyboard is not locked and that no procedure is in progress. 2. Hold the key “DOWN” for 1 s: the display will show the first label available. 3. Press and release the "UP" or "DOWN" key to select “rCH”. 4. Press and release the “SET” key. 5.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 12 SETTINGS 12.1 Setting the date, time and day of the week (only in the models with clock) The date can be set in the day-month-year format; the time in the hours-minutes format (24 h). To access the procedure: 1. Make sure that the keyboard is not locked and that no procedure is in progress. 2. Hold the key “DOWN” for 1 s: the display will show the first label available. 3.
EVCO S.p.A. 15. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 Press and release the key or the key within 15 sec to set: 16. - “Mon” (Monday) - “tuE” (Tuesday) - “UEd” (Wednesday) - “thu” (Thursday) - “Fri” (Friday) - “SAt” (Saturday) - “Sun” (Sunday). Press and release the “SET”: the "clock" LED shall turn off, and then the device shall exit the procedure. To exit the procedure before the operation is complete: 17. Do not operate for 60 sec (any changes will be saved). 12.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 To select a parameter: 7. Press and release the “UP” key or the “DOWN” key. To set a parameter: 8. Press and release the “SET” key. 9. Press and release the “UP” or “DOWN” key within 15 sec. Press and release the “SET” key and do not 10. operate for 15 s. To exit the procedure: 11.
EVCO S.p.A. 12.5 List of configuration parameters MIN. MAX. M.U. (4) EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 0.0 -18.0 0.0 -18.0 0.0 -18.0 0.0 -18.0 0.0 -18.0 0.0 -18.0 0.0 -18.0 0.0 -18.0 0.0 0.0 0.0 0.0 0.0 0.0 not avail. not avail. not avail. not avail. not avail. not avail. avail. not avail. 1 not avail. 1 not avail. 1 not avail. 1 not avail. 1 not 1 page 38 of 88 0.0 0 0.
EVCO S.p.A. P1 P2 P3 P4 P5 0 0 0 0 0 1 1 2 4 4 ---- ---- ---- ---- ---- 1 0 1 3 0 1 0 1 3 0 1 0 1 3 0 0 3 1 0 1 0 3 1 0 1 0 3 1 0 1 EVBOX1 | Installation guide ver. 1.
EVCO S.p.A. % 50 50 50 50 5 50 5 50 5 50 5 50 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 100 5 0 5 P7 5 percentage of the temperature detected by the inlet air for the calculation of the CPT temperature (only ifP4 = 4) (3) delay displaying temperature variation 5 pressure transducer minimum setting s/10 0 5 250 P8 5 not pressure transducer maximum setting avail.
r3 0.0 0 99.0 99.0 1 °C/°F (1) °C/°F (1) ---- 0.0 0.0 0 30 0.0 0.0 0 30 0.0 0.0 0 30 0.0 0.0 0 30 0.0 0.0 0 30 0.0 0.0 0 30 0.0 0.0 0 30 0.0 0.0 0 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 r4 0.0 30 EVCO S.p.A. r5 min 1 0 1 0 1 0 1 0 1 0 1 0 1 0 3 3 3 3 3 3 3 5 0 1 240 ---- 0 1 r6 0 min 3 page 41 of 88 5 EVB1256N9 5 EVB1246N9 5 EVB1236N9 5 EVB1226N9 5 EVB1216N9 5 EVB1206N9 5 EVB1214N9 r12 240 min M.U.
EVCO S.p.A. C3 C4 0 0 240 240 s min 0 10 0 10 0 10 10 0 10 0 10 0 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 0 10 0 10 80.0 10 80.0 90.0 10 80.0 90.0 10 80.0 90.0 10 80.0 90.0 10 80.0 90.0 10 80.0 90.0 10 80.0 90.0 10 °C/°F (1) 90.0 min 199 °C/°F (1) 240 0.0 199 0 C6 0.
EVCO S.p.A. C12 C13 C14 0 0 0 10 10 1 ---- ---- ---- 2 1 0 2 1 0 2 1 0 0 1 2 0 1 2 0 1 2 EVBOX1 | Installation guide ver. 1.
h (1) min 8 8 8 8 8 8 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 8 2.0 30 2.0 30 2.0 30 2.0 30 2.0 30 2.0 30 30 2.0 0 8 2.0 30 page 44 of 88 0 EVB1256N9 0 EVB1246N9 0 EVB1236N9 0 EVB1226N9 0 EVB1216N9 0 EVB1206N9 0 EVB1214N9 EVCO S.p.A. 99 ---- M.U. 0 2 MAX. d0 0 99.0 MIN. d1 -99 99 PARAM.
EVCO S.p.A. d4 d5 d6 d7 0 0 0 0 1 99 2 15 ---- min ---- min 0 0 1 2 0 0 1 2 0 0 1 2 2 1 0 0 2 1 0 0 2 1 0 0 EVBOX1 | Installation guide ver. 1.
EVCO S.p.A. d8 d9 d11 0 -99 0 4 99.0 1 ---- (1) °C/°F ---- 0 0.0 0 0 0.0 0 0 0.0 0 0 0.0 0 0 0.0 0 0 0.0 0 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 0 0.0 0 page 46 of 88 0 0.0 0 = = = = = in models EVB1204N9, EVB1206N9, times established in parameters Hd1...
EVCO S.p.A. d15 d16 d18 d19 d20 0 0 0 0.0 0 99 99 999 40.0 500 min min min °C/°F (1) min 0 0 40 3.0 180 0 0 40 3.0 180 0 0 40 3.0 180 180 3.0 40 0 0 180 3.0 40 0 0 180 3.0 40 0 0 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 0 0 40 3.0 180 page 47 of 88 0 0 40 3.
EVCO S.p.A. d21 d22 d25 d26 0 0.0 0 0 500 10.0 1 99 min °C/°F (1) ---- h 200 2.0 0 6 200 2.0 0 6 200 2.0 0 6 6 0 2.0 200 6 0 2.0 200 6 0 2.0 200 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 200 2.0 0 6 page 48 of 88 200 2.
M.U. ---- (1) 0 0 0 0 0 0 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 0 -10.0 0 -10.0 10.0 -10.0 10.0 -10.0 10.0 -10.0 10.0 -10.0 10.0 -10.0 10.0 -10.0 10.0 1 10.0 120 1 120 1 120 1 page 49 of 88 120 1 120 1 120 1 120 1 120 1 1 EVB1256N9 1 EVB1246N9 1 EVB1236N9 1 EVB1226N9 1 EVB1216N9 1 EVB1206N9 1 EVB1214N9 EVCO S.p.A. MAX. 1 MIN. 0 PARAM. A0 °C/°F 2 99.0 0 99.0 ---- -99.0 A2 -99.
240 min 15 15 15 15 15 15 15 15 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 0 EVCO S.p.A. A7 1 2.0 1 15 15 avail. not 2.0 avail. not 15 15 1 2.0 1 15 15 avail. not 2.0 avail. not 15 15 1 2.0 1 15 15 avail. not 2.0 avail. not 15 15 1 2.0 1 15 15 avail. not 2.0 15 15 min min 240 min 240 0 240 0 A9 0 A8 A10 ---- (1) °C/°F 15.0 2 0.
5 M.U. ---- °C/°F (1) ---- EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 1 -1.0 1 -1.0 1 -1.0 1 -1.0 1 -1.0 1 -1.0 1 -1.0 1 -1.0 0 page 51 of 88 0 EVB1256N9 0 EVB1246N9 0 EVB1236N9 0 EVB1226N9 0 EVB1216N9 0 EVB1206N9 0 EVB1214N9 EVCO S.p.A. 0 99.0 MAX. F0 -99.0 2 MIN. F1 0 PARAM.
EVCO S.p.A. F3 F4 F5 F6 F7 0 0 0 0 -99.0 15 240 240 1 99.0 min s s ---- °C/°F (1) 0 60 10 0 5.0 0 60 10 0 5.0 0 60 10 0 5.0 5.0 0 10 60 0 5.0 0 10 60 0 5.0 0 10 60 0 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 0 60 10 0 5.0 page 52 of 88 0 60 10 0 5.
0.1 (5) 15.0 EVCO S.p.A. F8 240 240 240 240 99.0 0 0 0 0 0.0 F9 F11 F12 F13 F14 (1) °C/°F s °C/°F (1) s sx10 sx10 2.0 2.0 2.0 2.0 2.0 2.0 2.0 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 2.0 0 30 30 30 15.0 0 30 30 30 15.0 0 30 30 30 15.0 0 30 30 30 15.0 0 30 30 30 15.0 0 30 30 30 15.0 0 30 30 30 15.0 0 15.
MIN. MAX. M.U. page 54 of 88 EVB1226N9 EVB1236N9 EVB1246N9 EVB1256N9 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 EVB1216N9 EVCO S.p.A. PARAM.
EVCO S.p.A. i0 0 5 ---- 3 3 3 3 3 3 EVBOX1 | Installation guide ver. 1.
EVCO S.p.A. i1 0 1 ---- 0 0 0 0 0 0 EVBOX1 | Installation guide ver. 1.
EVCO S.p.A. i5 0 9 ---- 7 7 7 7 7 7 EVBOX1 | Installation guide ver. 1.
EVCO S.p.A. i5 i6 i7 0 0 0 9 1 120 ---- ---- min 7 0 0 7 0 0 7 0 0 0 0 7 0 0 7 0 0 7 EVBOX1 | Installation guide ver. 1.
EVCO S.p.A. i8 i9 i10 i13 i14 0 1 0 0 0 15 999 999 240 240 ---- min min ---- ---- 0 240 0 180 32 0 240 0 180 32 0 240 0 180 32 32 180 0 240 0 32 180 0 240 0 32 180 0 240 0 EVBOX1 | Installation guide ver. 1.
EVCO S.p.A. i15 0 9 ---- 9 9 9 9 9 9 EVBOX1 | Installation guide ver. 1.
EVCO S.p.A. i15 i16 i17 0 0 0 9 1 240 ---- ---- s 9 0 30 9 0 30 9 0 30 30 0 9 30 0 9 30 0 9 EVBOX1 | Installation guide ver. 1.
MIN. MAX. M.U. page 62 of 88 EVB1226N9 EVB1236N9 EVB1246N9 EVB1256N9 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 EVB1216N9 EVCO S.p.A. PARAM.
EVCO S.p.A. u1 0 12 ---- 0 0 not avail. not avail. not avail. not avail. not avail. not EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 avail.
EVCO S.p.A. u1 0 12 ---avail. not avail. not 6 6 6 6 EVBOX1 | Installation guide ver. 1.
EVCO S.p.A. u2 u3 u4 u5 u6 u7 0 0 0 -99.0 1 -99.0 1 240 1 99.0 120 99.0 ---- s ---- (1) °C/°F min °C/°F (1) 0 10 1 -1.0 5 -5.0 0 10 1 -1.0 5 -5.0 0 10 1 -1.0 5 -5.0 0 10 1 -1.0 5 -5.0 0 10 1 -1.0 5 -5.0 0 10 1 -1.0 5 -5.0 0 10 1 -5.0 5 -1.0 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 0 10 1 -1.0 5 -5.
EVCO S.p.A. u9 u11 0 0 1 12 ---- ---- not 1 not avail. 1 avail. 1 3 3 1 3 1 3 1 EVBOX1 | Installation guide ver. 1.
EVCO S.p.A. M.U. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 not 1 not avail. 1 0 0 0 0 0 0 avail. not avail. not avail. not avail. not avail. not 0 0 0 0 0 0 0 page 67 of 88 avail. not avail. not avail. not avail. not avail. not 0 0 0 0 0 0 0 avail. not avail. not avail. not avail. not avail. not 0 0 0 0 0 0 0 avail. not avail. not avail. not avail. not avail. not 0 avail.
H13 H12 H11 H10 H09 H08 H07 H06 0 0 0 0 0 0 0 0 0 24 23 24 23 24 23 24 23 24 h h h h h h h h h EVCO S.p.A. H14 not avail. not avail. not avail. not avail. not avail. not avail. not avail. not avail. not avail. 0 0 0 0 0 0 0 0 0 not avail. not avail. not avail. not avail. not avail. not avail. not avail. not avail. not avail. avail. not avail. not avail. not avail. not avail. not avail. not avail. not avail. not avail.
Hd1 h0 h0 h-- h-- h-- h h h h not avail. not avail. not avail. not avail. not avail. not avail. h-- h-- h-- h-- h-- EVB1214N9 h-- not avail. not avail. not avail. not avail. not avail. not EVB1206N9 avail. page 69 of 88 avail. not avail. not avail. not avail. not avail. not avail. not EVB1226N9 h-- h-- h-- h-- h-- h-- EVB1236N9 avail. not avail. not avail. not avail. not avail. not avail.
247 2 247 2 247 2 247 2 247 2 247 EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 247 2 EVCO S.p.A. 247 2 M.U. ---- 2 MAX. 247 ---- MIN. 1 3 PARAM. LA 0 (1) The formula for the calculation of the CPT temperature is: Properly set the parameters corresponding to the regulators after setting parameter P2 the unit of measurement depends on P2 2 Lb (2) RS-485 MODBUS device address 2 1 0 = = = = 19.200 baud 9.600 baud 4.800 baud 2.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.
the condenser fan is on on condition that the compressor is on and is off when the temperature of the condenser drops below the temperature established with parameter F11 on condition that if parameter P4 is set at 0, 2, 3 or 4, the condenser fan will function in parallel with the compressor EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 (29) EVCO S.p.A.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 13 WARNING LIGHTS AND DIRECTIONS 13.1 Signals The following table shows the meaning of the LED warning lights of the device.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 Alarm LED light If the LED is on: - an alarm is in progress If the LED is flashing: - 13.2 compressor maintenance is required; see parameter C10 Signal Descriptions/Explanations The following table shows the meaning of the signal codes of the device. CODE Loc ---- MEANING - the keyboard is blocked; see paragraph 6.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 14 ALARMS 14.1 Alarms The following table shows the meaning of the alarm codes of the device.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 Compressor shut down alarm.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 15 ERRORS 15.1 Errors The following table shows the meaning of the error codes of the device.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 16 ACCESSORIES 16.1 Non opto-isolated RS-485/USB serial interface EVIF20SUXI 16.1.1 Preliminary notes The interface makes it possible to connect the device to the Parameters Manager set-up software system. 16.2 Data recorder EVUSBREC01 16.2.1 Preliminary notes The device records the board data and their download (via USB in a CSV file format). 16.3 USB cover for panel installation 0812000002 16.3.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 16.4 0810500018/0810500020 connection cable 16.4.1 Preliminary notes The cables can be used to connect the USB cover for panel installation 0812000002 to the EVUSBREC01 data recorder. The 0810500018 cable is 2.0 m long; the 0810500020 cable is 0.5 m long.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 17 TECHNICAL DATA 17.1 Technical data Purpose of the command device: operating command device. Construction of the command device: built-in electronic device. Container: grey self-extinguishing. Heat and fire protection class: D. Dimensions: 262.0 x 179.0 x 95.6 mm (10.314 x 7.047 x 3.763 in; L x H x D). Method of mounting the command device: wall mounted, with bolts and fastening screws. Shell protection grade: IP65.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 Humidity for use: from 10 to 90 % relative humidity without condensate. Command device pollution situation: 2. Height at which it is used: from 0 to 2,000 m (from 0 to 6,591 ft). Height at which it can be transported: from 0 to 3,048 m (from 0 to 10,000 ft). - RoHS 2011/65/CE Environmental standards: - WEEE 2012/19/EU - EMC standards: - EN 60730-1 - IEC 60730-1. 115...
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 according to model, up to 5 inputs: - 3 configurable via configuration parameter for OTC or NTC probes (room temperature, evaporator temperature and evaporation temperature) - 1 configurable via configuration parameter for PTC or NTC parameter probes for (configurable condenser via configuration temperature, critical temperature, evaporator 2 temperature or CPT temperature) - 1 for 4-20 mA transducers (vapour pressure).
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 according to model, up to 6 outputs: - 2 SPST electromechanical relays with 30 A res. @ 250 VAC (compressor and defrosting) - 2 SPST electromechanical relays with 16 A res. @ 250 VAC (evaporator fan and room light) - 1 SPST electromechanical relay with 8 A res.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124 EVBOX1 Front mounted electrical boards for cold rooms with single-phase compressor Installation guide ver. 1.2 PT - 25/14 Code 144BOX1E124 This document is exclusive property of EVCO; EVCO does not assume any liability regarding possible errors stated. The customer (manufacturer, installer or final user) assumes all liability regarding configuration of the device.