Instruction Manual

EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
page 23 of 88
u1
in the EVB1204N9 and EVB1214N9 models, the application is managed through
the K4 digital output
0
= man in cold room exit
1
= demister heating elements
2
= auxiliary output
3
= alarm output
4
= door heating elements
5
= neutral area operating heating elements
6
= condenser fan
7
= compressor 2
8 = defrosting2
9
= evaporator fan 2
10
= pump down valve
11
= on/stand-by
12
= man in cold room exit
0
u1
in the remaining models, the application is managed by the K5 digital output
0
= reserved
1
= demister heating elements
2
= auxiliary output
3
= alarm output
4
= door heating elements
5
= neutral area operating heating elements
6
= condenser fan
7
= compressor 2
8
= defrosting2
9
= evaporator fan 2
10
= pump down valve
11
= on/stand-by
12
= man in cold room exit
5
u11
if present, the application is managed by the K6 digital output
0
= reserved
1
= demister heating elements
2
= auxiliary output
3 = alarm output
4
= door heating elements
5
= neutral area operating heating elements
6
= condenser fan
7
= compressor 2
8 = defrosting2
9
= evaporator fan 2
10
= pump down valve
11
= on/stand-by
12
= man in cold room exit
2
Then, check that the remaining settings are appropriate; refer to paragraph 12.5 “List of configuration parameters”.
6.
Connect the loads power supply
7.
Turn the device on; refer to paragraph "Device switch-on/off in manual mode".
For additional information, please refer to the following paragraphs.