12.5 List of configuration parameters
The following table shows the meaning of the configuration parameters of the devices.
PARAM. MIN. MAX. M.U.
EVB1204N9
EVB1214N9
EVB1206N9
EVB1216N9
EVB1226N9
EVB1236N9
EVB1246N9
EVB1256N9
WORKING SETPOINT
SP r1 r2 °C/°F (1) -18.0 -18.0 -18.0 -18.0 -18.0 -18.0 -18.0 -18.0 Working set-point; see also r0
PARAM. MIN. MAX. M.U.
EVB1204N9
EVB1214N9
EVB1206N9
EVB1216N9
EVB1226N9
EVB1236N9
EVB1246N9
EVB1256N9
MEASUREMENT INPUTS
CA1 -25.0 25.0 °C/°F (1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
if P4 = 0, 1, 2 o 3, room temperature offset
if P4 = 4, inlet air temperature offset
CA2 -25.0 25.0 °C/°F (1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 evaporator temperature offset
CA3 -25.0 25.0 °C/°F (1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 auxiliary temperature offset (see P4)
CA4 -250 250
points/10
(4)
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
0 0 vapour pressure offset
CA5 -25.0 25.0 °C/°F (1)
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
0.0 0.0 evaporation temperature offset
P0 0 1 - - - - 1 1 1 1 1 1 1 1
temperature probe type
0 = PTC
1
= NTC