EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
page 39 of 88
P1 0 1 - - - - 1 1 1 1 1 1 1 1
degree Celsius decimal point
1
= YES
P2 0 1 - - - - 0 0 0 0 0 0 0 0
temperature unit of measurement (2)
0 = degree Celsius
1
= degree Fahrenheit
P3 0 2 - - - - 1 1 1 1 1 1 1 1
evaporator temperature probe function
0
= probe absent
1
= defrosting probe and probe for evaporator fan
thermostating
2
= probe for evaporator fan thermostating
P4 0 4 - - - - 3 3 3 3 3 3 3 3
magnitude recorded by the auxiliary temperature probe
0 = probe absent
1
= condenser temperature
2
= critical temperature
3
= evaporator 2 temperature
4
= outlet air temperature; in this case the
temperature associated with the setting shall be
the CPT (Calculated Product Temperature) one;
see also P7
P5 0 4 - - - - 0 0 0 0 0 0 0 0
magnitude displayed during normal operation
0
= if P4 = 0, 1, 2 or 3, room temperature
if P4 = 4, CPT temperature
1
= working set-point
2
= evaporator temperature
3
= temperature recorded by the auxiliary probe (see
P4)
4
= inlet air temperature (only if P4 = 4 )