Instruction Manual

EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
page 41 of 88
r3 0 1 - - - - 0 0 0 0 0 0 0 0
locking of working set-point setting (using the procedure
described in paragraph”Setting the working set point”)
1
= YES
r4 0.0 99.0 °C/°F (1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
working set point increase during the “energy saving"
function; see also i5, i10, i15, H01... H14
r5 0.0 99.0 °C/°F (1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
working set-point decrease during the “rapid cooling”
function; see also r6
r6 0 240 min 30 30 30 30 30 30 30 30 duration of “rapid cooling” function; see also r5
r12 0 1 - - - - 1 1 1 1 1 1 1 1
type of r0
0 = asymmetric
1
= symmetric
PARAM. MIN. MAX. M.U.
EVB1204N9
EVB1214N9
EVB1206N9
EVB1216N9
EVB1226N9
EVB1236N9
EVB1246N9
EVB1256N9
COMPRESSOR PROTECTION SYSTEM
C0 0 240 min 0 0 0 0 0 0 0 0
delay in switching on of compressor after the device
switches on (8)
C1 0 240 min 5 5 5 5 5 5 5 5
minimum time between two consecutive compressor
start-ups; also delay in compressor start-up after
conclusion of room temperature/inlet air probe error
(code “Pr1”) (9) (10)
C2 0 240 min 3 3 3 3 3 3 3 3 minimum compressor switch-off duration (9)