Instruction Manual
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
page 42 of 88
C3 0 240 s 0 0 0 0 0 0 0 0 minimum duration of compressor switch on time
C4 0 240 min 10 10 10 10 10 10 10 10
duration of compressor switch off time during a room
temperature/inlet air probe error (code “Pr1”); see also
C5
C5 0 240 min 10 10 10 10 10 10 10 10
duration of compressor switch on time during a room
temperature/inlet air probe error (code “Pr1”); see also
C6
C6 0.0 199 °C/°F (1) 80.0 80.0 80.0 80.0 80.0 80.0 80.0 80.0
condenser temperature is higher than that at which the
condenser overheating alarm is activated (code “COH”)
(11)
C7 0.0 199 °C/°F (1) 90.0 90.0 90.0 90.0 90.0 90.0 90.0 90.0
condenser temperature above which the blocked
compressor alarm is activated (code “CSd”)
C8 0 15 min 1 1 1 1 1 1 1 1 blocked compressor alarm delay (code “CSd”) (12)
C10 0 999 hx10 0 0 0 0 0 0 0 0
number of operating hours is higher than the limit at
which the need for maintenance is signalled
0
= function absent
C11 0 240 s 3 3 3 3 3 3 3 3
minimum time interval between the switching on of two
different compressors (only if u1 and/or u11 = 7)