Instruction Manual

EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
page 43 of 88
C12 0 10 - - - - 2 2 2 2 2 2 2 2
incidence of the number of compressor operation hours
on the choice of compressor to be switched on/off when
attempting to balance the number of operation hours and
the number of switch-ons of the two compressors ; see
also C13 (only if u1 and/or u11 = 7)
C13 0 10 - - - - 1 1 1 1 1 1 1 1
incidence of the switch-ons of the compressor on the
choice of compressor to be switched on/off when
attempting to balance the number of operation hours and
the number of switch-ons of the two compressors ; see
also C12 (only if u1 and/or u11 = 7)
C14 0 1 - - - - 0 0 0 0 0 0 0 0
type of pump down (only if u1 and/or u11 = 10)
0 = TIMED - the compressor and the pump down
valve shall be switched on at the same time due
to the setting; the pump down valve shall be
turned off due to the setting and the compressor
after the expiration of the u3 time interval from
the valve switch-off
1 = FROM DIGITAL INPUT - the compressor and the
pump down valve shall be switched on at the
same time due to the setting; the pump down
valve shall be turned off due to the setting and
the compressor afterwards and as a consequence
of the activation of the multifunction or
multifunction 2 input (only if i5 or
i15 = 6); see also u3