Instruction Manual

EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
page 44 of 88
PARAM. MIN. MAX. M.U.
EVB1204N9
EVB1214N9
EVB1206N9
EVB1216N9
EVB1226N9
EVB1236N9
EVB1246N9
EVB1256N9
DEFROSTING
d0 0 99 h 8 8 8 8 8 8 8 8
if d8 = 0, 1 or 2, defrosting interval (13)
0 = interval defrosting will never be activated
d8 = 3, maximum defrost interval
d1 0 2 - - - - 0 0 0 0 0 0 0 0
type of defrosting
0
= ELECTRIC - during defrosting the compressor will
remain off and the defrosting output will be
activated; evaporator fan activity will depend on
parameter F2
1
= BY HOT GAS - during defrosting the compressor
will be switched on and the defrosting output will
be activated; evaporator fan activity will depend
on parameter F2
2
= VIA STOPPING OF COMPRESSOR - during
defrosting the compressor will remain switched off
and the defrosting output will remain deactivated;
evaporator fan activity will depend on parameter
F2
d2 -99 99.0
°C/°F
(1)
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
temperature at end of defrosting (only if P3 = 1); see also
d3
d3 0 99 min 30 30 30 30 30 30 30 30
if P3 = 0 o 2, defrosting duration
se P3 = 1, maximum defrosting duration; see also d2
0
= defrosting will not be activated