Instruction Manual

EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
page 51 of 88
PARAM. MIN. MAX. M.U.
EVB1204N9
EVB1214N9
EVB1206N9
EVB1216N9
EVB1226N9
EVB1236N9
EVB1246N9
EVB1256N9
EVAPORATOR FAN AND CONDENSER FAN
F0 0 5 - - - - 1 1 1 1 1 1 1 1
evaporator fan activity during normal operation
0
= switched off
1
= switched on; see also F13, F14 and i10 (23)
2
= in parallel with the compressor; see also F9, F13,
F14 and i10 (24)
3
= depending on F1; see also F9, F13, F14 and i10
(25) (26)
4
= switched off if the compressor is switched off,
dependent on F1 if the compressor is switched on;
see also F9, F13, F14 and i10 (25) (27)
5 = depending on F6; see also F9
F1 -99.0 99.0
°C/°F
(1)
-1.0 -1.0 -1.0 -1.0 -1.0 -1.0 -1.0 -1.0
evaporator temperature above the limit at which the
evaporator fan is switched off (only if F0 = 3 o 4); see
also F8
F2 0 2 - - - - 0 0 0 0 0 0 0 0
evaporator fan activity during defrosting and dripping
0
= switched off
1
= switched on (setting parameter d7 to 0 is
recommended)
2
= depending on F0