Instruction Manual

EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
page 65 of 88
u2 0 1 - - - - 0 0 0 0 0 0 0 0
activation of room light switch on/off (in models
EVB1204N9 and EVB1214N9 only if u1 = 0) or of the
auxiliary output (in models EVB1204N9 and EVB1214N9
only if u1 = 2, in the remaining models only if u1 and/or
u11 = 2) in manual mode with the device turned off (40).
1
= YES
u3 0 240 s 10 10 10 10 10 10 10 10
if C14 = 0 compressor switch-off delay after pump down
valve switch-off
if C14 = 1 maximum delay between pump down valve
switch-off and compressor switch-off
u4 0 1 - - - - 1 1 1 1 1 1 1 1
enabling of alarm output deactivation with the silencing of
the buzzer (in models EVB1204N9 and EVB1214N9 only if
u1 = 3, in the remaining models only if u1 and/or u11 =
3)
1
= YES
u5 -99.0 99.0
°C/°F
(1)
-1.0 -1.0 -1.0 -1.0 -1.0 -1.0 -1.0 -1.0
room temperature or CPT temperature below which the
door heating elements are turned on ("u5 - 2.0°C/4°F in
models EVB1204N9 and EVB1214N9 only if
u1 = 4, in the remaining models only if u1 and u11 = 4).
u6 1 120 min 5 5 5 5 5 5 5 5
duration of demister heating elements activation (in
models EVB1204N9 and EVB1214N9 only if u1 = 1, in the
remaining models only if u1 and/or u11 = 1)
u7 -99.0 99.0
°C/°F
(1)
-5.0 -5.0 -5.0 -5.0 -5.0 -5.0 -5.0 -5.0
neutral area value (relative to the work set-point, i.e.
“work set-point + u7) (in models EVB1204N9 and
EVB1214N9 only if u1 = 5, in the remaining models only if
u1 and/or u11 = 5) (41)