Instruction Manual

EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
page 70 of 88
PARAM. MIN. MAX. M.U.
EVB1204N9
EVB1214N9
EVB1206N9
EVB1216N9
EVB1226N9
EVB1236N9
EVB1246N9
EVB1256N9
RS-485 MODBUS
LA 1 247 - - - - 247 247 247 247 247 247 247 247 device address
Lb 0 3 - - - - 2 2 2 2 2 2 2 2
baud rate
0
= 2.400 baud
1
= 4.800 baud
2
= 9.600 baud
3
= 19.200 baud
LP 0 2 - - - 2 2 2 2 2 2 2 2
parity
0
= none (no parity)
1
= odd
2
= even
Notes:
(1)
the unit of measurement depends on P2
(2)
Properly set the parameters corresponding to the regulators after setting parameter P2
(3)
The formula for the calculation of the CPT temperature is:
CPT temperature = {[(P7) x (temperature detected by the inlet air probe)] + [(100 - P7) x (temperature detected by the outlet air probe)] : 100}
(4)
the parameter is a dimensional and is expressed in tenths (for instance, 1 = 0.1 bar, 10 = 1 bar, etc...); the position of the decimal point depends on parameter P11 .
(5)
the value depends on parameter P2 (0,1 °C or 1 °F)
(6)
if parameter r12 is set to 0, the compressor will be switched on when the room temperature or CPT temperature is above the "working set-point + r0" and will be switched off when the
temperature falls below the working set-point; if parameter r12 is set to 1, the compressor will be switched on when the room temperature or CPT temperature is above the “working set-point
+ r0/2” and will be switched off when the temperature falls below the "working set-point - r0/2”