P1 0 1 - - - - 1 1 1 1 1 1 1 1
degree Celsius decimal point
1
=
YES
P2 0 1 - - - - 0 0 0 0 0 0 0 0
temperature unit of measurement (2)
0
=
degree Celsius
1
=
degree Fahrenheit
P3 0 2 - - - - 1 1 1 1 1 1 1 1
evaporator temperature probe function
0
=
probe absent
1
=
defrosting probe and probe for evaporator fan
thermostating
2
=
probe for evaporator fan thermostating
P4 0 4 - - - - 3 3 3 3 3 3 3 3
magnitude recorded by the auxiliary temperature probe
0
=
probe absent
1
=
condenser temperature
2
=
critical temperature
3
=
evaporator 2 temperature
4
=
outlet air temperature; in this case the
temperature associated with the setting shall be
the CPT (Calculated Product Temperature) one;
see also P7
P5 0 4 - - - - 0 0 0 0 0 0 0 0
magnitude displayed during normal operation
0
=
if P4 = 0, 1, 2 or 3, room temperature
if P4 = 4, CPT temperature
1
=
working set-point
2
=
evaporator temperature
3
=
temperature recorded by the auxiliary probe (see
P4)
4
=
inlet air temperature (only if P4 = 4 )