r4 0.0 99.0 °C/°F (1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
working set point increase during the “energy saving"
function; see also i5, i10, i15, H01... H14
r5 0.0 99.0 °C/°F (1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
working set-point decrease during the “rapid cooling”
function; see also r6
r6 0 240 min 30 30 30 30 30 30 30 30 duration of “rapid cooling” function; see also r5
r12 0 1 - - - - 1 1 1 1 1 1 1 1
type of r0
0
=
asymmetric
1
=
symmetric
PARAM. MIN. MAX. M.U.
EVB1204
EVB1214
EVB1206
EVB1216
EVB1226
EVB1236
EVB1246
EVB1256
ELECTRONIC EXPANSION VALVE (45)
h01 3.0 25.0 °C/°F (1)
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
6.0 6.0 superheating
h02 10.0 40.0 °C/°F (1)
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
15.0 15.0
evaporating temperature above which the high
superheating alarm is activated (code “HSH”) (11)
h03 -70.0 40.0 °C/°F (1)
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
non
disp.
-70.0 -70.0
evaporating temperature below which the low pressure
modality is activated (the valve is completely open; code
“LOP”) (11)
h04 1.0 99.9 °C/°F (1)
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
40.0 40.0 PID action proportional band
h05 0 999 s
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
120 120 PID action integral time