Manual

EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 46 of 92
PARAM. MIN. MAX. M.U.
EVB1204
EVB1214
EVB1206
EVB1216
EVB1226
EVB1236
EVB1246
EVB1256
COMPRESSOR PROTECTION SYSTEM
C0 0 240 min 0 0 0 0 0 0 0 0
delay in switching on of compressor after the device
switches on (8)
C1 0 240 min 5 5 5 5 5 5 5 5
minimum time between two consecutive compressor
start-ups; also delay in compressor start-up after
conclusion of room temperature/inlet air probe error
(code “Pr1”) (9) (10)
C2 0 240 min 3 3 3 3 3 3 3 3 minimum compressor switch-off duration (9)
C3 0 240 s 0 0 0 0 0 0 0 0 minimum duration of compressor switch on time
C4 0 240 min 10 10 10 10 10 10 10 10
duration of compressor switch off time during a room
temperature/inlet air probe error (code Pr1”); see also
C5
C5 0 240 min 10 10 10 10 10 10 10 10
duration of compressor switch on time during a room
temperature/inlet air probe error (code Pr1”); see also
C6
C6 0.0 199 °C/°F (1) 80.0 80.0 80.0 80.0 80.0 80.0 80.0 80.0
condenser temperature is higher than that at which the
condenser overheating alarm is activated (code COH”)
(11)
C7 0.0 199 °C/°F (1) 90.0 90.0 90.0 90.0 90.0 90.0 90.0 90.0
condenser temperature above which the blocked
compressor alarm is activated (code “CSd”)