Manual

EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 47 of 92
C8 0 15 min 1 1 1 1 1 1 1 1 blocked compressor alarm delay (code “CSd”) (12)
C10 0 999 hx10 0 0 0 0 0 0 0 0
number of operating hours is higher than the limit at
which the need for maintenance is signalled
0
=
function absent
C11 0 240 s 3 3 3 3 3 3 3 3
minimum time interval between the switching on of two
different compressors (only if u1 and/or u11 = 7)
C12 0 10 - - - - 2 2 2 2 2 2 2 2
incidence of the number of compressor operation hours
on the choice of compressor to be switched on/off when
attempting to balance the number of operation hours and
the number of switch-ons of the two compressors ; see
also C13 (only if u1 and/or u11 = 7)
C13 0 10 - - - - 1 1 1 1 1 1 1 1
incidence of the switch-ons of the compressor on the
choice of compressor to be switched on/off when
attempting to balance the number of operation hours and
the number of switch-ons of the two compressors ; see
also C12 (only if u1 and/or u11 = 7)