Manual

EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 50 of 92
d4 0 1 - - - - 0 0 0 0 0 0 0 0
defrosting when device is switched on (only if d8 = 0, 1, 2
or 3) (8)
1
=
YES
d5 0 99 min 0 0 0 0 0 0 0 0
if d4 = 0, minimum time between switching on of device
and activation of defrosting (8)
if d4 = 1, delay in activation of defrosting after device is
switched on (8)
d6 0 2 - - - - 1 1 1 1 1 1 1 1
temperature displayed during defrosting (only if P5 = 0)
0
=
room temperature or CPT temperature
1
=
if on activation of defrosting, the room
temperature or CPT temperature is below the
“work set point + t”, at maximum “ work set point
+ t”; if on activation of defrosting, the room
temperature or CPT temperature is above work
set point + t”, at maximum the room temperature
or CPT temperature on activation of defrosting
(14) (15)
2 = indication “dEF (16)
d7 0 15 min 2 2 2 2 2 2 2 2
during dripping the compressor will remain switched off
and the defrosting output will remain deactivated; if d16
= 0, evaporator fan activity will depend on parameter F2;
if d16 0, the evaporator fan will remain switched off)