Manual

EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 56 of 92
PARAM. MIN. MAX. M.U.
EVB1204
EVB1214
EVB1206
EVB1216
EVB1226
EVB1236
EVB1246
EVB1256
EVAPORATOR FAN AND CONDENSER FAN
F0 0 5 - - - - 1 1 1 1 1 1 1 1
evaporator fan activity during normal operation
0
=
switched off
1
=
switched on; see also F13, F14 and i10 (23)
2
=
in parallel with the compressor; see also F9, F13,
F14 and i10 (24)
3
=
depending on F1; see also F9, F13, F14 and i10
(25) (26)
4
=
switched off if the compressor is switched off,
dependent on F1 if the compressor is switched on;
see also F9, F13, F14 and i10 (25) (27)
5
=
depending on F6; see also F9
F1 -99.0 99.0
°C/°F
(1)
-1.0 -1.0 -1.0 -1.0 -1.0 -1.0 -1.0 -1.0
evaporator temperature above the limit at which the
evaporator fan is switched off (only if F0 = 3 o 4); see
also F8
F2 0 2 - - - - 0 0 0 0 0 0 0 0
evaporator fan activity during defrosting and dripping
0
=
switched off
1
=
switched on (setting parameter d7 to 0 is
recommended)
2
=
depending on F0