F3 0 15 min 0 0 0 0 0 0 0 0
maximum duration of evaporator fan deactivation; see
also F7 (during evaporator fan deactivation the
compressor can be switched on, the defrosting output will
remain deactivated and the evaporator fan will remain
switched off)
F4 0 240 s 60 60 60 60 60 60 60 60
duration of evaporator fan deactivation during operation
in low relative humidity conditions with the compressor
switched off; see also F5 (only if F0 = 5)
F5 0 240 s 10 10 10 10 10 10 10 10
duration of evaporator fan activation during operation in
low relative humidity conditions with the compressor
switched off; see also F4 (only if F0 = 5)
F6 0 1 - - - - 0 0 0 0 0 0 0 0
operation in low or high relative humidity conditions (only
if F0 = 5) (28)
0
=
low relative humidity (during operation in low
relative humidity conditions the evaporator fan
shall function in parallel with the compressor; see
also F4 and F5)
1
=
high relative humidity (during operation in high
relative humidity conditions the evaporator fan
shall be switched on)
F7 -99.0 99.0
°C/°F
(1)
5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
evaporator temperature below which the evaporator fan is
restarted (in respect to the working set point, that is to
say “working set-point + F7”); see also F3