i8 0 15 - - - - 0 0 0 0 0 0 0 0
number of multifunction input alarms (code iA”) such to
cause a pressure switch alarm (code iSd) (only if i5
and/or i15 = 3)
0 = function disabled
i9 1 999 min 240 240 240 240 240 240 240 240
time that must pass in absence of multifunction input
alarms (code “iA) so that the alarm counter is reset (only
i5 and/or i15 = 3)
i10 0 999 min 0 0 0 0 0 0 0 0
time that must pass in absence of door micro switch input
activations (after the room temperature or COT
temperature has reached the working set-point) for the
“energy saving” function to be activated (this impacts the
evaporator fan only if F0 = 1, 2, 3 or 4); see also r4, HE2
and H01... H14
0
=
the function will never be activated due to the
effect of this condition
i13 0 240 - - - - 180 180 180 180 180 180 180 180
number of door switch input activations such as to
provoke the defrost activation
0
=
defrosting will never be activated due to the effect
of this condition
i14 0 240 - - - - 32 32 32 32 32 32 32 32
minimum duration of the door switch input activation such
as to provoke the defrost activation
0
=
defrosting will never be activated due to the effect
of this condition