Par.
Min. Max. Unit Default Compressor protections
C0 0 240 min 0
minimum time between restoring the power supply after a
power cut, occurring during an operating cycle and
compressor switch-on
C1 0 240 min 5
minimum time between two consecutive compressor switch-
ons (3)
C2 0 240 min 3
minimum time between compressor switch-off and
successive switch-on (3)
C3 0 240 s 0 compressor switch-on minimum duration
C4 0 240 min 10
duration of compressor switch-off during the cabinet probe
error (“Pr1” code) that occurs during storage; see also
parameters C5 and C9
C5 0 240 min 10
duration of compressor switch-on during the cabinet probe
error (“Pr1 code) that occurs during post blast chilling
storage; see also parameter C4
C6 0 199 °C/°F (1) 80
condenser temperature above which the blocked
overheated condenser alarm is activated (“COH” code) (4)
C7 0 199 °C/°F (1) 90
condenser temperature above which the blocked
compressor alarm is activated (“CSd” code)
C8 0 15 min 1 blocked compressor alarm delay (“CSd” code) (5)
C9 0 240 min 30
duration of compressor switch-on during the cabinet probe
error (“Pr1 code) that occurs during post deep freezing
storage; see also parameter C4
Par.
Min. Max. Unit Default Defrosting (6)
d0 0 99 h 8
defrosting interval (7)
0 = defrosting will never be activated at intervals