F11 0 99 °C/°F (1) 15
condenser temperature above which the condenser fan is
switched on (intended as “F11 + differential and on
condition the compressor is switched off); see also
parameter F12 (4) (12)
F12 0 240 s 30
condenser fan switch-off delay from compressor switch-off
(only if parameter P5 is set at 0)
F15 0 240 s 15
evaporator fan delay from door closure, i.e. from the
deactivation of the door micro switch input
F16 -99 99 °C/°F (1) 20
evaporator temperature above which the evaporator fan is
off during pre-cooling, blast chilling and deep freezing (only
if parameter F0 is set at 1); see also parameter F8 (11)
F17 -99 199 °C/°F (1) 90
cabinet temperature above which the evaporator fan is off
during pre-cooling, blast chilling and deep freezing (only if
parameter F0 is set at 1 or 2); see also parameter F8
F18 0 100 % 20
evaporator fan speed 1 (intended as a percentage of the
maximum speed; sonly if parameter F0 is set at 3); see
paragraph 6.12 “Blast chilling/deep freezing intensity”
F19 0 100 % 40
evaporator fan speed 2 (intended as a percentage of the
maximum speed; only if parameter F0 is set at 3); see
paragraph 6.12 “Blast chilling/deep freezing intensity”
F20 0 100 % 60
evaporator fan speed 3 (intended as a percentage of the
maximum speed; sonly if parameter F0 is set at 3); see
paragraph 6.12 “Blast chilling/deep freezing intensity”
F21 0 100 % 80
evaporator fan speed 4 (intended as a percentage of the
maximum speed; sonly if parameter F0 is set at 3); see
paragraph 6.12 “Blast chilling/deep freezing intensity”
F22 0 100 % 100
evaporator fan speed 5 (intended as a percentage of the
maximum speed; sonly if parameter F0 is set at 3); see
paragraph 6.12 “Blast chilling/deep freezing intensity”