Manual

EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114
page 73 of 94
u6 1 240 min 5 switching on UV light for sterilisation cycle duration
u7 -99 199 °C/°F (1) 40
needle probe heating end temperature (temperature
detected by the needle probe); see also parameter u8
u8 0 240 min 2
maximum duration of needle probe heating; see also
parameter u7
0 = needle probe heating is disabled
u9 0 1 - - - - 1
needle probe heating on opening of the door, i.e. on
activation of the door entry micro switch, which occurs after
interruption of a blast chilling and storage cycle or a deep
freezing and storage cycle during storage.
1 = yes
u11 0 1 - - - - 0
utility managed by the output K7 (15)
0 = cabinet light (in this case, the DEEP FREEZING key
and parameters i0 will assume significance)
1 = UV light (in this case, the DEEP FREEZING key and
parameter u6 will assume significance)
u12 0 999 s 10
compressor switch off delay from pump down valve
deactivation (pump down in switch-off) (16)
Par.
Min. Max. Unit Default
Serial communication (RS-48 serial port with
MODBUS communication protocol)
L0 0 1 - - - - 0
operating mode
0 = slave (in this case, it will be possible to connect
Parameters Manager set-up software system, to the
monitoring and surveillance system of the RICS
plants or to the data recording device, to download
the recorded data to the port (via USB)
EVUSBREC01).
1 = master (in this case, it will be possible to connect the
print module PM 100A X9S001 to the port)
L1 1 240 min 5 print interval during blast chilling or during deep freezing
L2 1 240 min 15 print interval during storage
LA 1 247 - - - - 247 device address