14 ERRORS
14.1 Errors
The following table illustrates the meaning of the error codes.
Code Meaning
Pr1
Cabinet probe error.
Solutions:
- check the value of the parameter P0
- check the integrity of the probe
- check the device-probe connection
- check the temperature of the cabinet.
Main consequences:
- if the error occurs during the “stand-by” status, no operating cycles can be selected or started
- if the error occurs during blast chilling or deep freezing, the cycle will be interrupted
- if the error occurs during storage, compressor activity will depend on parameters C4 and C5 or
C9
- defrosting will never be activated
- the minimum temperature alarm (“AL” code) will never be activated
- the maximum temperature alarm (“AH” code) will never be activated
- the door heating elements will never be switched on
- the alarm output will be activated.
Pr2
Evaporator probe error.
Solutions:
- the same as the cabinet probe error (“Pr1” code) but relative to the evaporator probe.
Main consequences:
- if parameter P4 is set at 1, defrosting will last for the period of time established with parameter
d3
- if parameter F0 is set at 1, parameter F16 will have no effect
- if parameter F2 is set at 1, the device will operate as if it were set at 2.
- the alarm output will be activated.
Pr3
Condenser probe error.
Solutions:
- the same as the cabinet probe error (“Pr1” code) but relative to the condenser probe.
Main consequences:
- the condenser fan will operate parallel to the compressor
- the overheated condenser alarm (“COH” code) will never be activated
- the compressor blocked alarm (“CSd” code) will never be activated
- the alarm output will be activated.