C17 0 60 s not avail. 5 not avail.not avail. 5 not avail. 5 consecutive minimum duration of mains voltage permanence below C15 or above
C16, such to cause switch-off of the compressor
C18 0 60 - - - not avail. 5 not avail.not avail. 5 not avail. 5 consecutive number of compressor switch ons aborted due to mains voltage outside
of C14, C15 or C16, such to cause forced compressor switch-on (11)
0 = C4, C5 and C6 will not have effect
oo = the device will never perform forced compressor switch on
PARAM. MIN. MAX. U.M. EVR221 EVR261 EVR202 EVR203 EVR263 EVR204 EVR264 DEFROSTING
EVR231 EVR271 EVR232 EVR233 EVR273 EVR234 EVR274
d0099h8888888if d8 = 0, 1 or 2, defrosting interval (12)
0 = interval defrosting will never be activated
if d8 = 3, maximum defrost interval
d1 0 2 - - - not avail.not avail. 00000type of defrosting
0=
ELECTRIC - during defrosting the compressor will remain off and the
defrosting output will be activated; evaporator fan activity will depend on
parameter F2
1=
BY HOT GAS - during defrosting the compressor will be switched on and the
defrosting output will be activated; evaporator fan activity will depend on
parameter F2
2=
VIA STOPPING OF COMPRESSOR - during defrosting the compressor will
remain switched off and the defrosting output will remain deactivated;
evaporator fan activity will depend on parameter F2
d2 -99 99,0 °C/°F (1)not avail.not avail. 2,0 2,0 2,0 2,0 2,0 temperature at end of defrosting (only if P3 = 1); see also d3
d3 0 99 min 30 30 30 30 30 30 30 se P3 = 0 or 2, defrosting duration
se P3 = 1, maximum defrosting duration; see also d2
0 = defrosting will not be activated
d401- - -0000000defrosting on device switch-on (5)
1 = YES
d5099min0000000if d4 = 0, minimum time between switching on of device and activation of defrost-
ing; see also i0 and i5 (5)
if d4 = 1, delay in activation of defrosting after device is switched on ; see also i0 and
i5 (5)
d601- - -1111111temperature displayed during defrosting
0 = cell temperature
1 = if at the time of defrosting activation, the cell temperature is lower than the
“working set-point + r0”, at most “working set- point + r0”; if at the time
of defrosting activation, the cell temperature is higher than the “working
set-point + r0”, at most the cell temperature when defrosting is activated
d7 0 15 min not avail.not avail. 22222dripping duration (during dripping the compressor will remain switched off and the
defrosting output will remain deactivated; if d16 = 0, evaporator fan activity will
depend on parameter F2; if d16 ≠ 0, the evaporator fan will remain switched off)
d803 (14)- - -0000000defrosting activation methods
0=
AT INTERVALS - defrosting will be activated once the device has altogether
been running for time d0
1=
AT INTERVALS - FOR COMPRESSOR SWITCH-ON - defrosting will be acti-
vated once the compressor has altogether been switched on for time d0
2=
AT INTERVALS - FOR EVAPORATOR TEMPERATURE - defrosting will be
activated when the evaporator temperature has remained below the tem-
perature d9 for a total time of d0 (15)
3=
ADAPTABLE - defrosting will be activated at intervals, whose duration will
each time depend on the duration of compressor switch-ons and the
evaporator temperature; see also d18, d19 and d22 (15)
d9 -99 99,0 °C/°F (1)not avail.not avail. 0,0 0,0 0,0 0,0 0,0 evaporator temperature is higher than that at which the defrost interval counter is
suspended (only if d8 = 2)
d11 0 1 - - - not avail.not avail. 00000enabling of defrosting alarm concluded for maximum duration (code “dFd”; only if
P3 = 1 and in absence of an evaporator probe error (code “Pr2”)
1 = YES
d15 0 99 min not avail.not avail. 00000minimum time that the compressor must be switched on before defrosting can be
activated (only if d1 = 1) (16)
d16 0 99 min not avail.not avail. 00000predripping duration (during predripping the compressor will remain switched off, the
defrosting output will be activated and the evaporator fan will remain switched off)
d18 0 999 min not avail.not avail. 40 40 40 40 40 defrosting interval (only if d8 = 3; defrosting will be activated when the compressor
has been on totally, with the evaporator temperature below that of d22, for time
d18)
0 = defrosting will never be activated due to the effect of this condition
d19 0,0 40,0 °C/°F (1)not avail.not avail. 3,0 3,0 3,0 3,0 3,0 evaporator temperature above which the defrost is activated (relative to the evapo-
rator temperatures average, or “evaporator temperatures average - d19”) (only if
d8 = 3)
d20 0 500 min not avail.not avail. 180 180 180 180 180 minimum consecutive time the compressor must be switched on such as to provoke
the defrost activation
0 = defrosting will never be activated due to the effect of this condition
d22 0,0 10,0 °C/°F (1)not avail.not avail. 2,0 2,0 2,0 2,0 2,0 evaporator temperature above which the defrosting interval is suspended (relative
to the evaporator temperatures average, or “evaporator temperatures average +
d22”) (only if d8 = 3); also look at d18
PARAM. MIN. MAX. U.M. EVR221 EVR261 EVR202 EVR203 EVR263 EVR204 EVR264 TEMPERATURE ALARMS
EVR231 EVR271 EVR232 EVR233 EVR273 EVR234 EVR274
A0 0 1 - - - not avail.not avail. 00000temperature associated with the minimum temperature alarm (code “AL”)
0 = cell temperature
1 = evaporator temperature (17)
A1 -99 99,0 °C/°F (1) -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 temperature below that at which the minimum temperature alarm is activated (code
“AL”); see also A0, A2 and A11
A202- - -1111111type of minimum temperature alarm (code “AL”)
0 = alarm absent
1 = relative to working set-point (that is “working set-point - A1”; consider A1
without sign)
2 = absolute (that is A1)
A4 -99 99,0 °C/°F (1) 10,0 10,0 10,0 10,0 10,0 10,0 10,0 temperature higher than that at which the maximum temperature alarm is activated
(code “AH”); see also A5 and A11
A502- - -1111111type of maximum temperature alarm (code “AH”)
0 = alarm absent
1 = relative to working set-point (that is “working set-point + A4”; consider A1
without sign))
2 = absolute (that is A4)