Installer manual User Manual

EVCO S.p.A. EVXV 800 range | Installer manual ver. 1.2 | Code 144XV800E124
page 40 of 66
d7 0 15 min 2 2
dripping duration (the compressor and the
evaporator fan remain off during dripping and
the defrosting output will be deactivated)
d15 0 99 min 0 0
minimum duration of compressor switch-on
on activation of defrosting so these can be
activated (only if parameter d1 is set at 1) (8)
d16 0 99 min 0 0
duration of pre-dripping (only if parameter d1
is set at 1; the compressor and evaporator
fan will be off during pre-dripping and the
defrosting output will remain activated)
Par.
Min. Max. Unit
EVXV802
EVXV812
EVXV805
EVXV815
Temperature alarms (9) (10)
A1 0.0 99.0 °C/°F (1) 10.0 10.0
cabinet temperature below which the
minimum temperature alarm is activated
(relative to the work set-point, i.e. “r10 - A1”
during post blast chilling storage and “r11 -
A1” during post deep freezing storage; (“AL
code); also see parameter A11 (4)
A2 0 1 - - - - 1 1
enabling of minimum temperature alarm
(“AL” code)
1 = yes
A4 0.0 99.0 °C/°F (1) 10.0 10.0
cabinet temperature above which the
maximum temperature alarm is activated
(relative to the work set-point, i.e. “r10 +A4”
during post blast chilling storage and “r11
+A4” during post deep freezing storage;
(“AH” code); also see parameter A11 (4)
A5 0 1 - - - - 1 1
enabling of maximum temperature alarm
(“AH” code)
1 = yes
A7 0 240 min 15 15
temperature alarm delay (“AL code and
AH” code)