Installer manual User Manual

EVCO S.p.A. EVXV 800 range | Installer manual ver. 1.2 | Code 144XV800E124
page 41 of 66
A8 0 240 min 15 15
maximum temperature alarm delay (“AH
code) from the conclusion of evaporator fan
stop and storage start-up
A10 0 240 min
5
not
present in
EVXV802
model
5
not
present in
EVXV805
model
duration of a power cut such to cause the
power cut alarm to be memorised ( PF
code)when the power is supplied
0 = the alarm will not be signalled
AA 0 240 s 5 5
duration of buzzer activation on conclusion of
blast chilling and deep freezing
A11 0,1 15,0 °C/°F (1) 2,0 2,0 parameters A1 and A4 differential
A13 0 1 - - - -
1
not
present in
EVXV802
model
1
not
present in
EVXV805
model
memorisation of the temperature-controlled
blast chilling or temperature-controlled deep
freezing non concluded within maximum
duration alarm (“tiME” code)
1 = yes
Par.
Min. Max. Unit
EVXV802
EVXV812
EVXV805
EVXV815
Evaporator and condenser fan
F0 0 2 - - - - 1 1
evaporator fan activity during pre-cooling,
blast chilling and deep freezing
0 = off
1 = on; see also parameters F16 and F17
2 = parallel to the compressor; also see
parameters F9 and F17
F1 -50.0 99.0 °C/°F (1) -1.0 -1.0
evaporator temperature above which the
evaporator fan is off during storage (only if
parameter F2 is set at 3); also see parameter
F8 (11)