Installer manual User Manual
EVCO S.p.A. EVXV 800 range | Installer manual ver. 1.2 | Code 144XV800E124
page 42 of 66
F2 0 3 - - - - 3 3
evaporator fan activity during storage
0 = off
1 = on
2 = parallel to the compressor; also see
parameter F9
3 = on; also see parameter F1
F3 0 15 min 2 2
duration of evaporator fan standstill (the
compressor can be on during evaporator fan
standstill, the defrosting output will remain
deactivated and the evaporator fan will
remain off)
F8 0.1 15.0 °C/°F (1) 2.0 2.0 F1, F16 and F17 parameters differential
F9 0 240 s 0 0
evaporator fan switch-off delay from
compressor switch off (only if parameter F0
and/or parameter F2 are set at 2)
F11 0.0 99.0 °C/°F (1)
not
present
15.0
condenser temperature above which the
condenser fan is switched on (intended as
“F11 + differential and on condition that the
compressor is on); also see parameter F12
(4) (12) (13)
F12 0 240 s
not
present
30
condenser fan switch-off delay from
compressor switch-off
F15 0 240 s 15 15
evaporator fan delay from door closure, i.e.
from the deactivation of the door micro switch
input
F16 -50.0 99.0 °C/°F (1) 20.0 20.0
evaporator temperature above which the
evaporator fan is off during pre-cooling, blast
chilling and deep freezing (only if parameter
F0 is set at 1); also see parameter F8 (11)