PF
Power cut alarm (HACCP alarm; in EVXV812 and EVXV815 models only).
Solutions:
- check the device-power supply connection
- check the value of the parameter A10.
Main consequences:
- the device will memorise the alarm.
COH
Condenser overheated alarm.
Solutions:
- check the temperature of the condenser
- check the value of the parameter C6.
Main consequences:
- the condenser fan will be switched on.
CSd
Compressor blocked alarm.
Solutions:
- check the temperature of the condenser
- check the value of the parameter C7
- disconnect the device power supply and clean the condenser.
Main consequences:
- if the error occurs during the “stand-by” status, no operating cycles can be selected or started
- if the error occurs during an operating cycle, the cycle will be interrupted.
ESt
Configuration parameters download not completed successfully alarm.
Solutions:
- press and release a key to restore normal display
- download the configuration parameters again.
Main consequences:
- the device will continue to operate normally.
CEr
Configuration parameters firmware contained in EVKEY not coinciding with that of the device.
Solutions:
- cut the device power supply off
- check that the configuration parameters firmware contained in EVKEY coincides with that of the
device
- download the configuration parameters again.
Main consequences:
- the device will continue to operate normally.
Erd
Configuration parameters upload not completed successfully alarm.
Solutions:
- restore the factory settings
- upload the configuration parameters again.
Main consequences:
- the digital outputs will be switched off.