INTEGRITY SERIES K_NA4C3P21R Keep This Manual With Air Conditioner AIR CONDITIONER OPERATOR'S MANUAL CAUTION BEFORE INSTALLING AND USING THIS AIR CONDITIONER, IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY 900-039-42 KOOLTRONIC, INC. 30 Pennington-Hopewell Road Pennington, NJ 08534 609 • 466-3400 FAX: 609 • 466-1114 www.kooltronic.
TABLE OF CONTENTS Page I. Introduction 2 II. Incoming Inspection 3 III. Product Handling 3 IV. Product Identification Label 4 V. Principles of Operation 5-6 VI. Pre-Installation Testing 6 VII. Specific Model Data 7 - 10 Mounting Drawings and Dimensions Technical Data Major Component Replacements Standard Features Wiring Schematic VIII. Maintenance 11 - 12 IX. Trouble Shooting 13 X. Warranty 15 I.
II. Incoming Inspection Kooltronic Air Conditioners are designed, built and packaged to withstand the shock and vibration normally associated with shipment by common carriers. Occasionally improper handling during shipping causes damage. Such handling could include unbanding of palletized shipments, failing to respect "This Side Up" arrows, rough handling, falling off conveyors, excessive vibration, crushing, etc. Therefore, a thorough inspection should be done upon receipt of all shipments.
IV. Product Identification and Labels Each Kooltronic Air Conditioner includes an identification label. This label provides: ➀ ➁ ➂ ➃ ➄ ➅ ➆ ➇ Model Number Serial Number Electrical power characteristics Maximum and minimum ambient operating temperatures Cooling capacity Type and amount of refrigerant required for recharging Design Pressure Underwriters Laboratories Inc. Listed or Recognized Marks and NEMA ratings We recommend you copy this information from your unit. Air Conditioner MODEL NO. SERIAL NO.
V. Principles of Operation COOL AIR TO ENCLOSURE CONDENSER OUTLET (Heated Ambient Air Out) (2 Places) HEATED AIR FROM ENCLOSURE CONDENSER HEAT EXCHANGER EVAPORATOR HEAT EXCHANGER P21 COMPRESSOR CONDENSER AIR INLET (Ambient Air In) Kooltronic Air Conditioners are required when the equipment operating temperature must be kept near or lower than the ambient room temperature, and/or the cabinet must be sealed from dust, fumes, oil, corrosives and other contaminants.
The heater kit consists of a heater, a heat control thermostat and a heater limiter. The heater control thermostat is a bimetal disk with a fixed set point of 60°F. When the entering evaporator air temperature rises above 60°F the heater shuts off, and when the evaporator air temperature falls below 40°F the heater will engage. The contact points of the alarm thermostat are normally closed.
VII. Specific Model Data Mounting The Kooltronic Special Purpose Air Conditioners K_NA4C3P21R have been engineered to be installed easily. These units utilize double layer gaskets. The first gasket layer is placed on the outside perimeter of the front panel that is sealed against the customer enclosure. The second layer is placed on the two cutouts in the front panel. The first gasket layer will allow a small amount of water between the two layers.
Drawings and Dimensions FIGURE 1 MOUNTING PLAN 12.01 [305.0] CONDENSER OUTLET (Heated Ambient Air Out) (2 Places) 1.25 [31.7] 7.00 [177.8] 1.75 [44.4] COOL AIR TO ENCLOSURE (6) .312 [7.9] DIA. HOLES 20.09 [510.2] TYP. 21.19 [538.2] 7.94 [201.6] TYP. 7.00 [177.8] CONDENSER AIR INLET (Ambient Air In) 2.03 [51.5] TYP. 2.64 [67.0] 12.48 [316.9] .48 [12.1] HEATED AIR FROM ENCLOSURE 4.75 [120.6] TYP. Dimensions, inches [mm], are for reference only and are subject to change.
Technical Data BTU/H Capacity BTU/H 95°F/95°F Ambient Temp. °F Max. Ambient Temp. °F Min. Volts 3000 2160 125 0 K2NA4C3P21R 3000 2160 131 0 K2NA4C3P21R5 3000 1940 131 0 *Rating shown is for operation at maximum ambient temperature. Model KNA4C3P21R Hz Running Amps Approximate Weight (lbs.) 115 60 11.3 76 230 230 60 50 4.7 4.
Wiring Schematic WE BK GN EVAPORATOR FAN SUPPRESSOR 115 V 230 V T-STAT OPTIONAL SHORT CYCLE PROTECTOR OPTIONAL HEATER SHORT CYCLE TIMER THERMAL CUTOUT HEATER T-STAT SPEED CONTROLLER CONDENSER BLOWER MOTOR CAP. R C O/L S M S 2 1 COOLING EFFECT DETECTOR RELAY TO CUSTOMER CAP.
VIII. Maintenance Kooltronic Water-Cooled Air Conditioners require no maintenance. Air-Cooled Air Conditioners are designed to require only the routine cleaning of air filters to assure unimpeded airflow through the condenser heat exchanger. It is not possible to recommend specific filter cleaning intervals since the level and the nature of airborne particulate matter differs widely with each installation.
B. Blowers The design life of the blowers used in all Kooltronic Air Conditioners is substantially in excess of 20,000 hours. All Kooltronic condenser and evaporator blowers are equipped with automatic-reset thermal overload protectors. CAUTION Before opening the air conditioner, disconnect all power. If field replacement of a blower motor is necessary, most blower assemblies, including the mounting plate, are readily removable.
.IX. Trouble-Shooting Each Kooltronic Air Conditioner is engineered for performance and built for reliability. They are designed to require no routine maintenance other than the cleaning of ambient air filters. If your air conditioner should require warranty service, please contact Kooltronic. If you require service out of warranty, we have compiled a trouble-shooting chart to assist your service personnel. If additional assistance is required contact Kooltronic at (609) 466-3400.
This page intentionally left blank 14
X. Warranty KOOLTRONIC products are warranted to be free of defects in workmanship, materials and components.
BEAT THE HEAT! NE W! W! NE Motorized Impellers Delivers high CFM rates in a minimum amount of space. Basic and Packaged Blowers Basic units and packaged units for 19” EIA Rack; w/Grille, Filter and Guards. Capacities from 130 cfm to 1250 cfm. Advantage Air Conditioners and Heat Exchangers Ready for Indoor or Outdoor Installation Right Out of the Box! With rounded edges; no visible hardware and a textured baked powder finish to blend easily with contemporary enclosure designs.