System Reader Setting 
System reader can be used to acquire the card’s serial number when controller 
configures the card. User can set any reader that connects to the controller as the 
system reader. At the following submenu: 
Press 
ENT
 to enter System Reader setting. System will show current status of all 
readers as shown below. Y means the reader is the system reader, N means it’s not. 
By default, the first reader is set as the system reader. 
Press any of the 1-8 numeric keys to change the system reader setting of 
corresponding readers. Press   to exit. 
Door Setting 
Every door module controls two door relays. EFC-02 controller can control up to 8 
doors in total, defined as door 1 to 8 from left to right. According to card reader 
setting above, users can allocate multiple readers to one single door. User can directly 
set door open time, door held open time and the door control at fire alarm on the 
controller. 
Enter Door Setting Menu 
Under System menu, press 
 three times to bring up the following window: 
Press to enter Door Setting menu. Use 
 and 
 to choose from different menu 
options. All menu options under Door Setting are introduced below: 
Open Time Setting 
This sets the door open time when the card is swiped or open door button is pushed. 
The default time is 3 seconds. The maximal door open time supported by the 
controller is 999 minutes and 59 seconds. The door remains open as long as the open 
door button is pushed down. The door open time does not count until the button is 
released. At the following submenu: 
System Reader 
Setting 
12345678 
YNNNNNNN 
Door Setting 
Open Time 
Setting 
CLR 