Submittal Sheet

Table Of Contents
SBD Motor Actuator Specifications:
Operating Range - .1" - 2.4” W.C.
Pressure Sensor - Belimo D3 Dynamic Response
Air Pressure Connectors - 1/4” OD barbs integrated x2
Power - 24vac @ 4.0 volt/amp / 2.0 watt
Wiring - 18 AWG copper
Case - NEMA 3S, IP54
Gear Release - Manual
Maintenance: No Maintenance Required
Memory: Non-Volatile
Listings - UL, CE Compliance - ACCA Manual Zr
Pitot Tubes - Included x2
Pressure Tubing - 1/4” ID x 8’ (NSF-51) Included x2
Mounting - The SBD can be mounted horizontally,
vertically, or any other position required in the field.
TM
Forced Air Zone Controls
Model SBD
Self-Balancing
Smart Bypass Damper
SUBMITTAL SHEET
Connect to any M1 & M2
terminals, or to the “R” & “C”
terminals on any Ultra-Zone
zone control system, or field
transformer.
“SBD” SMART BYPASS DAMPER
FIELD WIRING
Field Wiring =
Factory Wiring =
WIRE
NUT
SBD
Motor
Actuator
385 Hwy. 33
Englishtown, NJ 07726
Ph: 800-446-3110
Fx: 732-446-5362
P/N 090377A0306 REV. G 11.26.14
CONTROLS INC.
E
W
Excellence Without Compromise
Copyright © EWC Controls Inc., 2014 All Rights Reserved
SUBMITTAL FORM
SUBMITTED BY:
JOB:
ARCHITECT:
ENGINEER:
CONTRACTOR:
LOCATION:
M2 or “R”
M1 or “C”
BLACK
RED
How the Smart Bypass Damper Works:
The Ultra-Zone Smart Bypass Damper captures
(with the push of a button) the total static
pressure of the HVAC system during non-zoned
mode, and modulates to maintain that same static
pressure value, during zoned mode. As individual
zone dampers open or close, the HVAC system static
pressure will fluctuate. In order to maintain the true
static pressure of the HVAC duct system during zoned
HVAC operations, a bypass duct with a reliable bypass
damper and a smart motor actuator must be installed.
No other bypass damper is easier to setup, than the
Ultra-Zone Smart Bypass Damper.
Description of the SBD Motor Actuator:
The Smart Bypass Motor Actuator is a digital
differential pressure controller with an integrated PI
loop and intelligent software. The Smart Bypass
Damper is the only industry bypass solution that
can automatically measure, monitor and maintain
the designed operating static pressure of the
HVAC system in all modes of operation.
The Smart Bypass Damper includes all of the
accessories needed for field installation.
No measuring instruments are required.
Submittal Specifications:
Furnish and install a Model SBD self-balancing
bypass damper manufactured by EWC Controls.
Round SBD’s are fabricated from 24 gauge
galvanized steel. Rolled shells include one female end
and one male (crimped) end, with rigid stiffening
beads. Includes pressure drop baffling for improved
damper authority and linear response. Round SBD’s
are equipped with a Poron® gasket on the blade.
*Specify model SBD - 8”, 10” , 12”, 14”, 16”,18”, 20”
Furnish and install a Model SBD self-balancing
bypass damper manufactured by EWC Controls.
Rectangular SBD’s shall be fabricated from mill
finished, extruded 080” aluminum and glass filled
nylon bearings. Includes pressure drop baffling for
improved damper authority and linear response.
*Specify model SBD - 12x8, 12x10, 12x12, 20x8
20x10, 20x12, etc.
*Custom sizing is available, call for details.
11
E
w
C
E
x
c
e
ll
e
nc
e
Wit
ho
ut C
o
mp
r
im
is
e
C
O
N
T
R
O
L
S
I
N
C
.
M
A
-
S
B
D
1
8
i
n
-
l
b
(
2
N
m
)
2
4
V
A
C
/
D
C
4
.
0
V
A
2
.
0
W
M
A
N
U
A
L
G
E
A
R
R
E
LE
A
S
E
E
wC
Excellence Without Comprimise
CONTROLS INC.
MADE IN SWITZERLAND
MA-SBD
18 in-lb (2Nm)
24 VAC/DC
4.0VA 2.0W
MANUAL
GEAR
RELEASE
0 1
1
2
-
+
POWER
BYPASS
SETUP
24vac Constant
Power Required
+
!
III
POWER
BYPASS
SETUP
!
I
I
I

Summary of content (2 pages)