Specifications

OUTPUT POWER - INVERTER MODE
INPUT - INVERTER MODE
GENERAL - INVERTER MODE
PROTECTION
CIRCUITRY
ENVIRONMENTAL
MECHANICAL
CONTINUOUS
POWER
NO LOAD
POWER
OUTPUT
VOLTAGE
OUTPUT
CURRENT
WEIGHT
LBS.
2000W
MODEL
VOLTAGE
SYSTEM
(TYPICAL)
MINIMUM
(TYPICAL)
MAXIMUM
(TYPICAL)
TYPICAL
EFFICIENCY
@ FULL
POWER
PEAK
EFFICIENCY
@ 1/2
POWER
12V 10.6V 13.8V
15V
> 88% > 90%
CONDITIONS MINIMUM TYPICAL MAXIMUM
WAVEFORM - SINUSOIDAL -
LINE REGULATION - .1% 2%
LOAD REGULATION - 1% 2%
DISTORTION - 1.5% 2%
FREQUENCY -.1% 60Hz +.1%
Over Voltage: Shutoff at maximum input
voltage, per input table.
Under Voltage: Shutoff at minimum input
voltage, per input table.
Thermal: 105 C internal
temperature.
Output Short: Unit shuts off:
electronically limited.
Manual reset required.
Temperature:
Humidity: 5 to 95% non-condensing
Cooling: Thermostatically controlled
variable speed forced air
Finish: Powder coated
Warranty: Two years parts and labor.
o o
-25 C to +25 C full power,
o
derated -17% @ 50 C then
o o
20% per 10 C above 50 C.
MCX/ICX POWER INVERTER SPECIFICATIONS
42V 55.2V 60V > 88% > 90%
57.8V 75.9V 82.5V > 88% > 90%
SURGE
POWER
4000W
120 +/-2%
10W
16.6 A
15
Case size: 18L x 9W x 4H
Weight: 15 lbs.
66V
48V
24V 21V 27.6V 30V > 88% > 90%
CHARGER MODE - CHARGING CURRENT
GENERAL - INVERTER MODE
CONDITIONS MINIMUM TYPICAL MAXIMUM
WAVEFORM SINUSOIDAL -
LINE REGULATION - .1% 2%
LOAD REGULATION - 1% 2%
DISTORTION - 1.5% 2%
FREQUENCY -.1% 60Hz +.1%
GENERAL - INVERTER MODE
CONDITIONS MINIMUM TYPICAL MAXIMUM
WAVEFORM SINUSOIDAL -
LINE REGULATION - .1% 2%
LOAD REGULATION - 1% 2%
DISTORTION - 1.5% 2%
FREQUENCY -.1% 60Hz +.1%
I MAX
12V
50A*
24V
33.3A
48V
16.6A
66V
12.1A
> 0.98
INPUT POWER FACTOR
BATTERY VOLTAGE
FLOAT VOLTAGE
MINIMUM
TYPICAL
MAXIMUM
10.6V
42V
57.8V
21V
15.2V
60V
82.5V
30V
13.4V
26.8V
53.6V
80.4V
*Specifications subject to change.