quickly. It will automatically restart when it has cooled sufficiently,
and the LOW BATT/THERM alarm will clear. 105 C internal
temperature. Warning buzz 5 C before shut off”.
XP-2000
C
o
OVERPOWER, SHORT CIRCUIT PROTECTION:
LED LEGEND:
.
.
.
.
.
.
.
.
.
.
.
The inverter has
three levels of overpower protection. The first limits peak
instantaneous current. The second system limits absolute power
coming from the module. Both of these circuits act to reduce output
voltage as required, to limit current to a safe level. The overpower
protection circuit will recover instantly when the overpower condition
clears. The third, is short circuit protection. If the over current
condition is so severe that it causes output voltage to collapse to 1
Vp for more than 1 second, the inverter will shut down and not
automatically restart. This requires the user to clear the short circuit
safely, and guarantee that hazardous voltage will not come back on
line until desired. To reset the inverter from this condition, cycle
power switch “OFF” then “ON” again.
inverterswillprovidepeakcurrent(45 A)ormaximumsurge
(4000W) for 3 seconds when the inverters internal temperature
is at or below 25 .The output power is then reduced to 2000W
(rated power) for 4 secs.
If the inverter cannot restore a full sine
wave due to overload, the LED will be red. If the overload condition
does not clear in 7 secs. allowed, the inverter shuts off (flashing red
indicator).
* LED will be red in overload and /or short circuit conditions. *
Solid Green (Inverter ON”)
Solid Orange (Over Temperature Warning)
Flashing Orange (Over temperature)
Solid Red (Overload Warning condition)
Flashing Red (Overload condition)
Fast Flashing Red (Internal Error condition)
---------
---------
---------
. . . . . .