® INSTALLATION & OPERATING INSTRUCTIONS FOR TCX TUBULAR LEAD-CALCIUM BATTERIES SECTION 93.
YOUR GNB INDUSTRIAL POWER REPRESENTATIVE SALESPERSON ________________________________ TELEPHONE____________________________________ LOCATION______________________________________ GNB SERVICE ASSISTANCE 1-800-241-4895
Page SECTION 1 1.0 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 SECTION 2 2.0 Receiving Batteries . . . . . . . . . . . . . . . . . . . .2 SECTION 3 3.0 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 SECTION 4 4.0 Battery Assembly and Installation . . . . . . . . .2 4.1 Site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 4.2 Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . .2 4.3 Temperature . . . . . . . . . . . . . . . . .
material or staining from leaking electrolyte would indicate rough handling. If such conditions are found, make notation on delivery receipt before signing. If battery damage is found, request an inspection by the carrier and file a damage claim. Also notify your GNB® Industrial Power representative.
connecting the battery string to the charger/load, measure the total voltage at the battery terminals. The voltage should be equal to the number of cells times the voltage of one cell. For example, 60 cells times 2.09 volts per cell = 125.40 volts (1.250 SG) or 60 cells times 2.05 volts per cell = 123.0 volts (1.215 SG). 4.3 TEMPERATURE A battery location having an ambient temperature of 25°C (77°F) will result in optimum battery life.
decreases as the battery is discharged and increases as the battery is recharged. TABLE A – Initial Charge Voltage per Cell (VPC) and Time after Current Stabilization for 1.215 and 1.250 SG TCX VPC 2.32 Time (hours) 1.215 SG 1.250 SG 222 412 2.35 166 304 2.38 126 222 2.41 96 164 2.42 88 148 2.50 42 78 6.2 Specific gravity is expressed to the third decimal place, e.g.1.250, and is measured by a hydrometer float enclosed in a glass barrel/rubber bulb syringe.
The correction factor is added to the measured battery voltage above 77°F(25°C). The correction factor is subtracted from the measured battery voltage below 77°F(25°C). indicator of the battery condition between scheduled overall individual cell readings. 11.2 It is recommended that a different pilot cell be selected each year to provide a representative specific gravity for the battery. Example: Cell Voltage Readings Cell Temperature 2.300 2.300 2.
® A Division of Exide Technologies GB-1000F WHEN ADVICE IS DESIRED PLEASE FORWARD A DUPLICATE OF THIS REPORT TO YOUR GNB REPRESENTATIVE 6
STATIONARY BATTERY PLASTIC CELL NUMERAL APPLICATION To insure proper adhesion of the pressure sensitive plastic cell numerals, and polarity markings supplied with your GNB® Flooded Classic Battery, the following procedure should be followed: 4. Numerals are shipped mounted on a plastic backing strip. They are easily removed by peeling back the plastic strip. Keep finger contact with adhesive backing on numeral to a minimum. 1.
NOTES 8
GNB Industrial Power – The Industry Leader. ® GNB Industrial Power, a division of Exide Technologies, is a global leader in network power applications including communication/data networks, UPS systems for computers and control systems, electrical power generation and distribution systems, as well as a wide range of other industrial standby power applications.