Datasheet

DBL_NYY.PDFIssue01.11.2013 Klaus Faber AG, 66113 Saarbrücken, Lebacher Str. 152-156, Tel.: (0681) 9711-0, FAX: - 289
Power cable NYY-J/-
O acc. to VDE 0276-603
conductor material: bare copper
conductor construction: class 1, from 25 sqmm class 2
insulation: PVC DIV 4
sheathing material: PVC DMV 5
colour of outer sheath: black
meter mark: yes
flame retardant: VDE 0482-332-1-2/IEC 60332-1
UV-resistant: yes
maximum temperature at
conductor:
70 °C
max. operating temperature,
fixed:
70 °C
temperature, moved/during
installation:
-5 - +70 °C
NYY-J NYY-O
nominal voltage Uo: 600 V 600 V
nominal voltage U: 1 kV 1 kV
maximum permitted
operating voltage in 3-phase
systems:
1,2 kV 1,2 kV
test voltage: 4 kV 4 kV
Application: For fixed installation in buildings, in free air, in ground and in water.
Switzerland: TT
Denmark: PVILD
Austria: E-YY
Russia: ВВГ
The products and information presented here are for technical calculation only. They are subject to technical progress and in no way represent the
ability of shipment. Outer diameters are approximately.
Core identification
number of cores with protective conductor without protective conductor
1 green-yellow black
2 - blue, brown
3 green-yellow, blue, brown brown, black, grey
4 green-yellow, brown, black, grey blue, brown, black, grau
5 green-yellow, blue, brown, black, grey blue, brown, black, grey, black
Table: Technical characteristics NYY-J
p/n part name
.
R
l.
[Ω/km]
W
i.
[mm]
I
bl.
[A]
I
be.
[A]
I
k.
[kA]
L
b.
[mH/km]
R
bv.
[mm]
W
m.
[mm]
D
A.
[mm]
F
zv.
[N]
Cu
.
[kg/km]
G
.
[kg]
011840 NYY-J 01X4 SW RE 4,61 1 0,46 0,459 136,5 1,8 9,1 200 38 110
011742 NYY-J 01X6 SW RE 3,08 1 0,69 0,431 142,5 1,8 9,5 300 58 130
010133 NYY-J 01X10 SW RE 1,83 1 1,15 0,399 153 1,8 10,2 500 96 180
010116 NYY-J 01X16 SW RE 1,15 1 1,84 0,371 168 1,8 11,2 800 154 240