Datasheet

dbl_nh9.pdfIssue24.03.2017 · Klaus Faber AG · Lebacher Straße 152 – 156 · 66113 Saarbrücken · Germany · Phone +49 681 9711-0 · Fax -289
FRNC power cable (N)HXH
FE180/E90 acc. to VDE 0266
conductor material: bare copper
conductor construction: class 1, from 25 sqmm class 2
insulation: FRNC compound HI1
sheathing material: FRNC-compound HM1
colour of outer sheath: orange
flame retardant: VDE 0482-266-2-4/IEC 60332-3-24 (Kat. C)
smoke density: DIN EN 61034/IEC 61034
halogen free: DIN EN 50267/IEC 60754
fire resistance: FE 180, EN 50200, EN 50362
circuit integrity: E 90
maximum temperature at
conductor:
90 °C
max. operating temperature,
fixed:
-5 - +70 °C
bending radius, fixed
installation:
12 x DA
(N)HXH-O E90 (N)HXH-J E90
nominal voltage Uo: 600 V 600 V
nominal voltage U: 1 kV 1 kV
maximum permitted
operating voltage in 3-phase
systems:
1,2 kV 1,2 kV
test voltage: 4 kV 4 kV
core identification: colours acc. VDE 0293 (HD308) colours acc. VDE 0293 (HD308)
Application: For installation in dry and wet rooms, also for direct bedding in concrete, butnot for direct burial in
ground and not for use in water. The cable has improved flame retardant and may be used in public buildings with
high safety requirements. Cables are halogen free, low smoke density and are fire resistant according to VDE 0472
part 814 (180 min., = IEC 60331), EN 50200 and EN 50362. Furthermore the cable passed the test of 90 min. circuit
integrity according to DIN 4102 part 12 (E 90) for all so called standard-installation systems (ladder, tray and ceiling).
A special test certificate about the circuit integrity is issued by the "Amtlichen Materialprüfanstalt für das Bauwesen".
For calculation of electrical systems with circuit integrity has to bee considered that electrical resistance of copper
conductors at 1000 °C is approximately 4,5 times higher than at 20 °C and the current carrying capacity has to be
reduced respectively.
The products and information presented here are for technical calculation only. They are subject to technical progress and in no way represent the
ability of shipment. Outer diameters are approximately.