Datasheet

DBL_NH3.PDFIssue01.11.2013 Klaus Faber AG, 66113 Saarbrücken, Lebacher Str. 152-156, Tel.: (0681) 9711-0, FAX: - 289
FRNC power cable NHXH
FE180/E30 acc. to VDE 0266
conductor material: bare copper
conductor construction: class 1, from 25 sqmm class 2
insulation: FRNC compound HI1
sheathing material: FRNC-compound HM1
flame retardant: VDE 0482-266-2-4/IEC 60332-3-24
smoke density: DIN EN 61034/IEC 61034
halogen free: DIN EN 50267/IEC 60754
fire resistance: FE 180 (IEC 60331)
circuit integrity: E 30
maximum temperature at
conductor:
90 °C
max. operating temperature,
fixed:
-5 - +70 °C
bending radius, fixed
installation:
12 x DA
nominal voltage Uo: 600 V
nominal voltage U: 1 kV
maximum permitted
operating voltage in 3-phase
systems:
1,2 kV
test voltage: 4 kV
core identification: colours acc. VDE 0293 (HD308)
Application: For installation in dry and wet rooms, also for direct bedding in concrete, but not for direct burial in ground
and not for use in water. The cable has improved flame retardant and may be used in public buildings with high safety
requirements. Cables are halogen free, low smoke density and are fire resistant according to VDE 0472 part 814
(180 min., = IEC 60331). Furthermore the cable passed the test of 30 min. circuit integrity according to DIN 4102 part
12 (E 30) for all so called standard-installation systems (ladder, tray and ceiling) and is suitable for installation in fire
alarm systems, safety lightning and other emergency electrical supply systems according to VDE 0108. A special test
certificate about the circuit integrity is issued by the "Amtlichen Materialprüfanstalt für das Bauwesen". For calculation
of electrical systems with circuit integrity has to bee considered that electrical resistance of copper conductors at 800
°C is approximately four times higher than at 20 °C and the current carrying capacity is reduced respectively.
The products and information presented here are for technical calculation only. They are subject to technical progress and in no way represent the
ability of shipment. Outer diameters are approximately.
Table: Technical characteristics NHXH-J/-O E30
p/n part name
.
R
l.
[Ω/km]
I
bl.
[A]
R
bv.
[mm]
D
A.
[mm]
Cu
.
[kg/km]
G
.
[kg]
011238 NHXH-O E30 01X4 RE OR RE 4,61 42 120 6,9 38 100
011240 NHXH-O E30 01X6 RE OR RE 3,08 53 135 7,9 58 120
011229 NHXH-O E30 01X10 RE OR RE 1,83 73 150 8,1 96 160
011232 NHXH-O E30 01X16 OR 1,15 97 180 8,9 154 200
011235 NHXH-O E30 01X25 RM OR RM 0,727 135 195 10,9 240 310
011237 NHXH-O E30 01X35 RM OR RM 0,524 165 225 11,9 336 410
011239 NHXH-O E30 01X50 RM OR RM 0,387 201 240 12,9 480 540

Summary of content (3 pages)