Data Sheet
© 2022 · Klaus Faber AG · all rights reserved KLAUS FABER AG · Europaallee 33 · 66113 Saarbrücken · Germany · T +49 681 9711 - 0 dbl_nymst.pdf / Issue 02/17/2022 / page 1/2
Screened building wire
(N)YM(St)-J
Application: This installation cable is statically shielded for limiting the electromagnetic elds of current-carrying conductors in
sensitive environments such as IT, hospitals, but also for installation in homes where a particular sensitivity to electromagnetic
elds is provided. For installation on, over, in and under plaster in dry, humid and wet rooms as well as in masonry and concrete
(except for shaken, jolted, tamped concrete). Also for use outdoors if protected from direct sunlight.
Construction and technical data:
CPR-classication according to EN 50575: Eca
Conductor material: copper, bare
Conductor construction: class 1, up from 16 sqmm class 2
Insulation: PVC TI1
Screen: Foil
Drain wire: yes
Sheathing material: PVC YM1
Colour of outer sheath: grey RAL 7035
Flame-retardant: VDE 0482-332-1-2/IEC 60332-1-2
Max. temperature at conductor, °C: 70 °C
Permitted outer cable temperature, xed, °C: 70 °C
Permitted outer cable temperature, moved, °C: 5 - 70 °C
The products and information presented here are for technical calculation only. They are subject to technical progress and in no way represent the ability of
shipment. Outer diameters are approximately.
(N)YM(St)-J
Nominal voltage Uo: 300 V
Nominal voltage U: 500 V
Test voltage: 2 kV
Protective conductor: yes
Core identication: colours acc. to VDE 0293 (HD308)
part
no.
part name Dl
[mm]
Rl
[Ohm/km]
Ibl
[A]
Rbv
[mm]
Ø
[mm]
Cu G
[kg]
020308 3X1.5 RE 1.5 12.1 15 45 9 51 154