Datasheet

dbl_yjz.pdfIssue24.03.2017 · Klaus Faber AG · Lebacher Straße 152 – 156 · 66113 Saarbrücken · Germany · Phone +49 681 9711-0 · Fax -289
Control cable YSLY-JZ/-JB/-OZ/-OB
conductor material: bare copper
conductor construction: fine stranded, class 5
insulation: PVC TI1
stranding unit: core
sheathing material: PVC TM2
colour of outer sheath: gray RAL 7001
flame retardant: VDE 0482-332-1-2/IEC 60332-1-2
maximum temperature at
conductor:
70 °C
max. operating temperature,
fixed:
-40 - +70 °C
temperature, moved/during
installation:
-5 - +70 °C
bending radius, fixed
installation:
4 x DA
bending radius, moved
application:
15 x DA
YSLY-JZ YSLY-OZ YSLY-JB YSLY-OB
nominal voltage Uo: 300 V 300 V 300 V 300 V
nominal voltage U: 500 V 500 V 500 V 500 V
test voltage: 2 kV 2 kV 2 kV 2 kV
protective conductor: yes no yes no
core identification: gn-ye + numbers numbers colours acc. VDE
0293 (HD308)
colours acc. VDE
0293 (HD308)
Application: Flexible power, process control and instrumentation cable for industry and mechanical engeneering in
indoor applications. For installation in dry and damp rooms. The cable is resistant against most usual chemicals, oil
and grease. Not suitable for permanent motion.
Additional information: Note: Please check also the UV-resistant version Y-JZ 600.
The products and information presented here are for technical calculation only. They are subject to technical progress and in no way represent the
ability of shipment. Outer diameters are approximately.
Table: Technical characteristics YSLY-JZ
p/n part name R
l.
[Ω/km]
D
A.
[mm]
Cu
.
[kg/km]
G
.
[kg/km]
030643 YSLY-JZ 03X0,5 GR 39 5,1 14,4 47
030644 YSLY-JZ 04X0,5 GR 39 5,7 19,2 58
030645 YSLY-JZ 05X0,5 GR 39 6,2 24 75
030647 YSLY-JZ 07X0,5 GR 39 6,8 33,6 93
030648 YSLY-JZ 08X0,5 GR 39 7 38 115