Data Sheet

© 2022 · Klaus Faber AG · all rights reserved KLAUS FABER AG · Europaallee 33 · 66113 Saarbrücken · Germany · T +49 681 9711 - 0 dbl_h1z2z2-k.pdf / Issue 02/17/2022 / page 1/2
Solar cable
FABER
®
SOLAR H1Z2Z2-K
Application: Solar line for freely movable use or xed installation in photovoltaic systems as per EN 60364-7-712. The cable
may be used indoors, outdoors, in explosive areas, in industrial or agricultural operations and is approved for direct laying in the
ground. The cable is regarded as short-circuit-proof and earth leakage-proof. It meets the VDE application regulation VDE-AR-E
2283-4. The cable has been subjected to the following additional tests: - abrasion as per EN 50289-3-7 - water AD 7 as per HD
516. Please note the applicable installation instructions on our website.
Construction and technical data:
CPR-classication according to EN 50575: Eca
Standard: VDE 0283-618
Conductor material: tinned copper
Conductor construction: Class 5 = exible
Insulation: cross-linked polyolen-copolymer
Sheathing material: cross-linked polyolen-copolymer
Flame-retardant: VDE 0482-332-1-2/IEC 60332-1-2
Smoke density: DIN EN 61034/IEC 61034
Halogen-free: DIN EN 50267/IEC 60754
UV-resistant: yes
Ozone-resistant: yes
For outdoor use: yes
Max. temperature at conductor, °C: 120 °C
Permitted outer cable temperature, xed, °C: -40 - +90 °C
Permitted outer cable temperature, moved, °C: -25 - +60 °C
Bending radius, xed installation: 4 x Ø
Bending radius, moving application: 6 x Ø
The products and information presented here are for technical calculation only. They are subject to technical progress and in no way represent the ability of
shipment. Outer diameters are approximately.