dbl_h1z2z2-k.pdfIssue24.03.2017 · Klaus Faber AG · Lebacher Straße 152 – 156 · 66113 Saarbrücken · Germany · Phone +49 681 9711-0 · Fax -289
Solar cable FACAB SOLAR
H1Z2Z2-K acc. to VDE 0283-618
conductor material: tinned copper
conductor construction: fine stranded, class 5
insulation: cross-linked polyolefin-copolymer
sheathing material: cross-linked polyolefin-copolymer
flame retardant: VDE 0482-332-1-2/IEC 60332-1-2
smoke density: DIN EN 61034/IEC 61034
halogen free: DIN EN 50267/IEC 60754
oil resistant: EN 60811-2-1
ozone resistant: yes
maximum temperature at
conductor:
120 °C
max. operating temperature,
fixed:
-40 - +90 °C
temperature, moved/during
installation:
-25 - +60 °C
bending radius, fixed
installation:
4 x DA
bending radius, moved
application:
6 x DA
nominal voltage Uo: 1 kV
nominal voltage U: 1 kV
nominal voltage (DC): 1,5 kV
test voltage: 6,5 kV
Application: For free movable or fixed installation in photovoltaic installations according to EN 60364-7-712. Cable
may be used indoor, outdoor, in explosion hazard areas in industry and agriculture. Direct earth burial is permitted. The
cable is considered to be short-circuit and earth-fault safe. It meets requirements of VDE-AR-E 2283-4. Please follow
the relevant installation guidelines!
The products and information presented here are for technical calculation only. They are subject to technical progress and in no way represent the
ability of shipment. Outer diameters are approximately.
Table: Technical characteristics H1Z2Z2-K
p/n part name D
l.
[mm]
R
l.
[Ω/km]
I
bl.
[A]
D
A.
[mm]
F
zv.
[N]
Cu
.
[kg/km]
G
.
[kg/km]
041027 H1Z2Z2-K 01X4 black 3 5,09 55 5,4 60 38,4 56
041028 H1Z2Z2-K 01X4 blue 3 5,09 55 5,4 60 38,4 56
041029 H1Z2Z2-K 01X4 red 3 5,09 55 5,4 60 38,4 56
041030 H1Z2Z2-K 01X6 black 3,9 3,39 70 5,9 90 58 74
041031 H1Z2Z2-K 01X6 blue 3,9 3,39 70 5,9 90 58 74
041032 H1Z2Z2-K 01X6 red 3,9 3,39 70 5,9 90 58 74
041033 H1Z2Z2-K 01X10 black 5,1 1,95 98 6,9 150 96 117

Summary of content (2 pages)