Rubber cable
H07RN-F
Application: For use at medium mechanical stress in dry, wet and damp locations, as well as outdoors. Also for xed installa-
tion on plaster or machines. The cable is oil-, UV- and ozone-resistant. Higher conductor temperatures may be permissible with
protected installation, please inquire. When installed in pipes or similar enclosed systems, the use of the cable is permitted up to
and including 1000 V AC voltage or up to 750 V DC voltage against earth.
Construction and technical data:
CPR-classication according to EN 50575: Eca
Standard: EN 50525-2-21
Conductor material: copper, bare
Conductor construction: Class 5 = exible
Insulation: rubber (EPR) EI4
Sheathing material: rubber (CR) EM2
Flame-retardant: VDE 0482-332-1-2/IEC 60332-1-2
UV-resistant: yes
Oil-resistant: EN 60811-404
Ozone-resistant: yes
For outdoor use: yes
Max. temperature at conductor, °C: 60 °C
Permitted outer cable temperature, xed, °C: -25 - +55 °C
Permitted outer cable temperature, moved, °C: -25 - +55 °C
The products and information presented here are for technical calculation only. They are subject to technical progress and in no way represent the ability of
shipment. Outer diameters are approximately.
Bending radius acc. DIN EN 50565-1
application <8 mm 8-12 mm 12-20 mm >20 mm
xed installation 3D 4D
free movement 5D 6D
cable entry 5D 6D