Datasheet

dbl_nsgafou.pdfIssue24.03.2017 · Klaus Faber AG · Lebacher Straße 152 – 156 · 66113 Saarbrücken · Germany · Phone +49 681 9711-0 · Fax -289
Rubber insulated wire NSGAFÖU
acc. to VDE 0250 T. 602
conductor material: tinned copper
conductor construction: fine stranded, class 5
insulation: rubber (EPR) 3GI3, halogen-free
sheathing material: rubber (CR) 5GM5
flame retardant: VDE 0482-332-1-2/IEC 60332-1-2
ozone resistant: yes
maximum temperature at
conductor:
90 °C
max. operating temperature,
fixed:
-40 - +80 °C
temperature, moved/during
installation:
-25 - +80 °C
NSGAFÖU 1,8/3 kV NSGAFÖU 3,6/6 kV
nominal voltage Uo: 1,8 kV 3,6 kV
nominal voltage U: 3 kV 6 kV
test voltage: 6 kV 11 kV
Application: This wire is designed for application in dry rooms, busses and railborn vehicles. If used in distribution or
switching appliances the wire is considered to be short circuit proof. It is resistant against most oils and grease.
The products and information presented here are for technical calculation only. They are subject to technical progress and in no way represent the
ability of shipment. Outer diameters are approximately.
Table: Technical characteristics NSGAFÖU 1,8/3 kV
p/n part name D
l.
[mm]
R
l.
[Ω/km]
I
bl.
[A]
R
bb.
[mm]
R
bv.
[mm]
D
A.
[mm]
F
zv.
[N]
Cu
.
[kg/km]
G
.
[kg/km]
050194 NSGAFOEU 01X1,5 1,8/3 kV
SW
1,8 13,7 30 27,5 22 5,5 23 14,4 60
050178 NSGAFOEU 01X2,5 1,8/3 kV
SW
2,4 8,21 41 29,5 23,6 6,2 38 24 70
050159 NSGAFOEU 01X4 1,8/3 kV
SW
3 5,09 55 32 25,6 6,7 60 38 90
050165 NSGAFOEU 01X6 1,8/3 kV
SW
3,9 3,39 70 35 28 7,2 90 58 120
050172 NSGAFOEU 01X10 1,8/3 kV
SW
5,1 1,95 98 42 33,6 8,7 150 96 180
050183 NSGAFOEU 01X16 1,8/3 kV
SW
6,3 1,24 132 46 36,8 10 240 154 250
050184 NSGAFOEU 01X25 1,8/3 kV
SW
7,8 0,795 176 57,5 46 12 375 240 390
050163 NSGAFOEU 01X35 1,8/3 kV
SW
9,2 0,565 218 64 51,2 13 525 336 470

Summary of content (2 pages)