Datasheet

dbl_iysty.pdfIssue24.03.2017 · Klaus Faber AG · Lebacher Straße 152 – 156 · 66113 Saarbrücken · Germany · Phone +49 681 9711-0 · Fax -289
Telecommunication cable J-
Y(St)Y ... Lg acc. to VDE 0815
conductor material: bare copper
conductor construction: solid, class 1
insulation: PVC TI1
stranding unit: pair
stranding: layers
screen over strand: foil
drain wire: yes
sheathing material: PVC TM1
colour of outer sheath: gray RAL 7032
flame retardant: VDE 0482-332-1-2/IEC 60332-1-2
max. operating temperature,
fixed:
-30 - +70 °C
temperature, moved/during
installation:
-5 - +50 °C
bending radius, fixed
installation:
7,5 x DA
bending radius, single bend: 2,5 x DA
insulation resistance: 100 MOhmxkm
coupling K1: 300 pF
operating capacity: 100 nF/km
nominal voltage U: 300 V
core identification: colours acc. VDE 0815
Application: For connection of telecommunication units inside of buildings in dry and wet rooms, also outdoors if the
cable is protected against direct sun irradiation. Not for use in power circuits!
Additional information: Stranding: cores twisted into pairs (2-pairs cable stranded as star-quad), pairs stranded in
layersCore identification: two-pair cable: red, black, white, yellow. More than two-pairs are in continuous sequence:
white-blue, white-yellow, white-green, white-brown, white-black. In the 1-st pair of each layer tehere is one red core red
in place of the white one.
The products and information presented here are for technical calculation only. They are subject to technical progress and in no way represent the
ability of shipment. Outer diameters are approximately.
Table: Technical characteristics I-Y(St)Y .. Lg
p/n part name D
A.
[mm]
G
.
[kg/km]
Cu
.
[kg/km]
100001 J-Y(St)Y 01X2X0,6 GR 5 30 7
100003 J-Y(St)Y 02X2X0,6 GR 5,5 35 13
100005 J-Y(St)Y 03X2X0,6 GR 6,3 50 18
100007 J-Y(St)Y 04X2X0,6 GR 6,8 55 24
100009 J-Y(St)Y 05X2X0,6 GR 7,2 65 30
p/n part name D
A.
[mm]
G
.
[kg/km]
Cu
.
[kg/km]
100011 J-Y(St)Y 06X2X0,6 GR 7,5 75 35
100013 J-Y(St)Y 08X2X0,6 GR 8 90 46
100017 J-Y(St)Y 10X2X0,6 GR 9 110 58
100019 J-Y(St)Y 12X2X0,6 GR 9,5 130 71
100021 J-Y(St)Y 14X2X0,6 GR 10 150 82